Aube Technologies manual Installation, Summary, MODEL TH111GFCI-NP 120 VAC, Options Selection

Models: TH111GFCI-NP

1 2
Download 2 pages 57.59 Kb
Page 1
Image 1
MODEL TH111GFCI-NP 120 VAC

MODEL TH111GFCI-NP 120 VAC

SUMMARY

OPTIONS SELECTION

At the back of the thermostat, there is one selection switches to set at your preferences.

Temperature in °C or °F.

TO SET TEMPERATURE

Press on SUMMARY or OPTIONS SELECTION once to see setpoint temperature appear on display. Every subsequent press will change the setpoint temperature by one degree.

TO RECORD THE INSTALLATIONManual backgroundManual background (COMFORT) SETPOINT TEMPERATURE

Select chosen setpoint

temperature by using

or

button. Press

on

button (2 to 3 seconds) until icon appears on display.

 

 

TO RECORD THE

(ECONOMIC) SETPOINT TEMPERATURE

 

Select chosen setpoint

temperature by using

or

button. Press

on

button (2 to 3 seconds) until icon appears on display .

 

 

TO RECORD THE

(VACATION) SETPOINT TEMPERATURE

 

To program the Vacation temperature, select the desired degree using the

buttons and press on the

and

buttons simultaneously until the

icon is displayed (app. 3 seconds).

 

 

CHECKING GROUND FAULT CIRCUIT INTERRUPTER (GFCI)

Adjust the setpoint temperature until heating indicator (flames) appears on display. Press TEST button. The test is conclusive if the warning light (GFCI) on thermostat is ON and power to the load is cut-off (flames remain on display though). If these events do not occur, check the installation. Press on RESET but- ton to reset the GFCI.

INSTALLATION

Parts included:

One (1) TH111GFCI-NP (120 VAC) thermostat

Two (2) 6-32 screws

Four (4) Solderless connectors (for copper wire)

One (1) Temperature sensor with a 15 foot extension

TURN OFF POWER TO THE HEATING SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. KEEP AIR VENTS OF THE THERMOSTAT CLEAN AND OBSTRUCTION FREE.

This thermostat should be installed by an electrician or experienced technician. The thermostat must be used with a circuit breaker or fuse.

This thermostat was designed to control floor electric heating systems. The resistive load must not exceed 2000 watts @ 120 VAC (16.7 A). The thermostat is equipped with a ground fault circuit interrupter (GFCI) and therefore the isolation of the line and load is required for operation. The polarity of line connection must be respected. During a ground fault, only the current in the black wire of the load will be cut-off from the 120 V line. Connect thermostat as shown on diagram.

1) CONNECTING WIRES AND MOUNTING THERMOSTAT

Connect the rear thermostat wires to the power supply and to the load using solderless connectors for copper wires. See schematic diagram.

Push the excess wire back into the electrical box to prevent interference withthe thermostat. Secure the thermostat using two (2) 6-32 screws 1 1/4 inches long. Once the thermostat is properly installed, return power to heating system.

2) CONNECTING TEMPERATURE SENSOR WIRE

Connect the sensor wire to the two lower screws of the terminal block at the back of the thermostat (no polarity need to be respected). The wire must pass outside the electrical box and follow the wall down to the floor. The sensing probe should be placed in a representative heat area for maximum system perfomance. The sensing probe should be centered between the wires in the mat. The probe wire cannot cross any heater wires and the temperature sensor must not be directly or adjacent to a heating wire.

120 VAC

60 HZ

CHOOSING THE TEMPERATURE SCALE IN °C (CELSIUS) OR °F (FAHRENHEIT) TO APPEAR ON DISPLAY.

Set the temperature switch at the back of the thermostat to °C or °F at your preferences.

720-111715-B 1/2

Page 1
Image 1
Aube Technologies manual Installation, Summary, MODEL TH111GFCI-NP 120 VAC, Options Selection