1.8Test & Commission.

After the wiring has been completed re-connect the battery to the terminals marked Batt + -

The panel will now go into alarm condition, enter user code (0123) to silence, the Tamper and Power will be lit and Day & Zone LED’s flashing.

To reset the panel re-enter the user code and the Day & Power LED’s will be steady (DAY mode).

Re-fit the lower cover and the system should now be tested to ensure correct operation.

2 Descriptions

2.1Zones

Avanti panels come supplied with service links fitted to the zone terminals to simulate a closed circuit. As each zone is connected these links should be removed. All zones are fully programmable.

Zone Functions per Program:

Immediate – This function would be used when the zone is not part of an entry/exit route. When the system is SET activation of an immediate zone will cause a full alarm condition.

Timed – A timed zone would be used to protect an entry/exit route. Opening the door or triggering the sensor in this type of zone when the system is SET will start the entry timer.

Time Inhibited – A time inhibited zone operates as an immediate zone unless a timed zone has been operated and a timer started. Such a zone would be utilised to allow passage between the entry/exit door and the control panel when there are detectors present.

Fire – If you choose to utilise a zone as a fire zone then no other devices may be wired into this zone. Therefore a zone cannot be both fire and intruder.

Doorbell –this feature can be programmed into any zone. A doorbell will not operate whilst the entry/exit timers have started, when the system is in full alarm condition or whilst in programming mode.

Exit Modes per Program:

Timed Exit – a timed program will SET once the exit timer has expired.

Final Door Set – a final door program will SET 5 seconds after the final door has been opened and closed.

Immediate/Silent Set – an immediate program will SET the system immediately and silently.

2.2 Tamper

Avanti panels come supplied with a service link fitted to the Tamper terminals; this should be removed as the tamper circuit is wired.

Tamper circuits must be wired in series.

If a Tamper occurs whilst the system is in DAY mode then only the internal sounders will be activated.

If a Tamper occurs whilst the system is SET then both the internal and external sounders will be activated. (If you are using an RS Panel fitted with a communicator then a signal will also be sent to an Alarm Receiving Centre (ARC).

2.3PA

Remove the service link and wire in series any number of PA buttons to the PA terminals. Activation of the PA will cause the system to go into a full alarm condition whether in DAY mode or SET. (If you are using an RS Panel fitted with a communicator then a signal will also be sent)

2.4Bell output & Strobe

Connect the wires from the bell to the terminals D (bell positive) and B (bell negative).

The bell tamper should be wired to the T A terminals and the service link removed.

Wire the strobe to the terminals marked strobe observing the correct polarity.

When fitting a combined sounder/strobe unit follow manufactures instructions.

T

-Ve tamper return

A

-Ve supply (0V)

B

-Ve sounder trigger

D

+Ve supply (12V)

2.5Internal sounder

A maximum of two 16 ohm extension speakers may be

wired in parallel to the terminals marked The volume of both the internal sounder and entry/exit timers can be adjusted by a pre-set located on the PCB.

2.6Set +

This output becomes 12V positive on SET and is removed on commencement of the entry timer.

2.713V Supply

This terminal provides a 13.8V output to power detectors and shock sensors etc. Total current available is 350 mA.

2.8PTS

The PTS terminals can be programmed to be either PUSH TO SET (PTS) or KEYSWITCH operation.

PTS – operation of an exit terminate button when exiting the property will cause the timer to expire immediately and the system will become SET.

Keyswitch – this enables the system to be SET and UNSET with the use of a keyswitch. If the panel needs to be reset then a user code must be entered.

2.9Battery

To ensure continuing protection in the event of mains power failure a suitable rechargeable battery with a capacity to support the system for a period of 12 hours must be fitted.

Battery Backup Time Vs. Number of Passives (Passive

Current=10ma)

 

19

 

 

 

 

 

1.2Ah Battery

Hours

 

 

 

 

 

 

14

 

 

 

 

 

2.1Ah Battery

 

 

 

 

 

 

 

Time in

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

Backup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

Number of Passives

Battery Backup Time Vs. Number of Passives (Passive

Current=15ma)

 

19

 

 

 

 

 

1.2Ah Battery

Hours

 

 

 

 

 

 

 

 

 

 

 

 

2.1Ah Battery

14

 

 

 

 

 

 

 

Time in

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

Backup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

Number of Passives

NOTE: Calculations made for Avanti Compact with onboard keypad using a neon sounder, assuming 1 complete alarm cycle of 20 minutes.

Page 2
Image 2
Avanti K-600HW manual Descriptions