Avanti K-600HW Remote signalling, Test Menu, Walk Test, Setting Up the System Flags, 13V output

Models: K-600HW

1 8
Download 8 pages 30.79 Kb
Page 6
Image 6
4.9 Test Menu.

4.9 Test Menu.

The Test Menu is entered from the Engineers menu by pressing Key 9. The alarm panel has several test modes making life a little easier for the installation engineer. They are as follows:

Press 1 to switch bell drive on.

Press 2 to switch strobe drive on.

Press 3 to switch all speakers on.

Press 0 to switch all outputs off.

Press 6 to enter walk test.

Press 9 to show zone status.

Press Z To Exit the Walk Test menu.

On entering the Test menu, All the zone LED’s will be switched off, and the PA and Tamper LED’s will be flashing, indicating a test must be selected.

WALK TEST.

On entering the zone walk test, all of the zones will be reset, and all zone LED’s will be switched off. The PA and Tamper LED’s will be flashing indicating that the engineer is within the walk test function.

Each time a zone is activated or de-activated the internal sounders will bleep. When a zone becomes active, the zone LED’s for all active zones will be lit.

Press Z To exit walk test. This will move you back to the test menu, the PA and Tamper LED’s will flash. To return to Engineer Menu Press Key Z.

4.10Setting Up the System Flags.

Set up System Flags menu is entered from the Engineers menu, by pressing KEY 0.

There are 3 system flags that can be set to tailor the way that the system operates.

On entering the set-up system flags menu, zones 2 and 3 LED’s will be lit according to the zone attributes that are selected. The flags are as follows:

LED 2 On for Bell follow.

LED 3 On for Key switch operation (PTS input). LED 3 Off for Push to set (PTS input).

Pressing the Key number that represents the LED number will toggle that attribute.

Press A To Accept / Press B To Abort the changes.

4.11 Viewing the Event Log.

The Event Log menu is entered from the engineers menu, by pressing key.

The Day LED will be extinguished to indicate Event Log mode.

The Zone, PA and Tamper LED’s will now show the latest event. Whichever Zone, PA or Tamper LED is flashing is the first activated, and whichever Zone, PA or Tamper is lit was triggered after the first event, but before the system was un-set.

To navigate through the event log, the following keys are used:

Press 1 To Jump to the oldest event. Press 2 To move to 1 event older. Press 3 To move to 1 event newer. Press 4 To Jump to the newest event. Press 9 To Reset the event log.

Press Z To Return to Engineer Menu.

If there are less than 16 events, then it is only possible to scroll between the number of events within the event log.

4.12Changing Chime in Day Mode

Chime is a low security attribute that can be programmed onto any zones. In Day mode, the Chime Attribute for each of the 8 zones may be changed in the following manner:

Press

All of the zones that will chime when they are activated will have the LED for that zone lit up.

Press the key that represents the zone that the zone attribute requires changing for. This will toggle the LED for that zone. When the LED is lit, that zone will chime when it is activated.

Once the changes have been made then:

Press A To Accept / Press B To Abort the changes.

5 Remote signalling

Communicator Terminals

The RS variant of the control panel is fitted with communicator outputs on the top left side of the PCB.

13V output

This output, along with the 0V output provides power for a wire on communicator, which is fused at 0.5A.

Note: Care should be taken to ensure that the maximum load on the power supply is less than 350ma for auxiliary devices such as communicators, passives but excludes the Bell/Strobe outputs.

Line Fail

This input allows the communicator to inform the panel that there is a line fault.

When the panel is in DAY mode a line fail will cause the Tamper LED to flash but will not cause an alarm.

A line fault when the panel is SET will not cause an alarm, but will cancel any bell delay programmed into the panel.

Outputs

There are 6 outputs labelled FIRE, PA, INT, SET, ABORT, and CONF. Each output sits at 12V when not active and is pulled to approximately 0.8V when active. Each output can sink 50ma, giving enough energy to drive a relay if required. These outputs would normally be connected to a STU or communicator.

FIRE – This output becomes active (0V) when the panel is activated by a fire input.

PA – This output becomes active (0V) when the panel is triggered by:

1)PA input becoming active

2)Duress code being entered

INT – This intruder output becomes active (0V) when the panel is triggered whilst the panel is SET.

SET – This output becomes active (0V) when the panel is SET.

ABORT – This output becomes active (0V) when an alarm condition is reset.

CONF – This confirmed output becomes active (0V) when 2 or more zones are triggered when the panel is SET.

Note: If the communicator or STU is being powered by a separate power supply, the 0V of the external power supply must be connected to the 0V of the alarm panel.

Page 6
Image 6
Avanti K-600HW Remote signalling, Test Menu, Walk Test, Setting Up the System Flags, Viewing the Event Log, 13V output