Appendix
Table of Recommended Alarm Settings
Refrigerant | Leak PPM | Spill PPM | Evacuate PPM |
|
|
|
|
R11 | 100 | 300 | 500 |
|
|
|
|
R12 | 100 | 300 | 500 |
|
|
|
|
R22 | 100 | 300 | 500 |
|
|
|
|
R23 | 100 | 300 | 500 |
|
|
|
|
R113 | 100 | 300 | 500 |
|
|
|
|
R114 | 100 | 300 | 500 |
|
|
|
|
R123 | 25 | 35 | 35 |
|
|
|
|
R124 | 100 | 300 | 500 |
|
|
|
|
R134a | 100 | 300 | 500 |
|
|
|
|
R401a | 100 | 300 | 500 |
|
|
|
|
R402a | 100 | 300 | 500 |
|
|
|
|
R402b | 100 | 300 | 500 |
|
|
|
|
R404a | 100 | 300 | 500 |
|
|
|
|
R407a | 100 | 300 | 500 |
|
|
|
|
R407c | 100 | 300 | 500 |
|
|
|
|
R409a | 100 | 300 | 500 |
|
|
|
|
R410a | 100 | 300 | 500 |
|
|
|
|
R500 | 100 | 300 | 500 |
|
|
|
|
R502 | 100 | 300 | 500 |
|
|
|
|
R503 | 100 | 300 | 500 |
|
|
|
|
R507 | 100 | 300 | 500 |
|
|
|
|
R508b | 100 | 300 | 500 |
|
|
|
|
H1301 | 100 | 300 | 500 |
|
|
|
|
Allowable Exposure Level (AEL) ASHRAE
Instruction | 27 |