Bacharach 3015-4256 manual Specifications, Halon

Models: 3015-4256

1 36
Download 36 pages 11.09 Kb
Page 34
Image 34
Specifications

Specifications

Product Type

Multiple refrigerant gas monitoring system for low level continuous monitoring

 

of refrigerant gases

Gas Library

CFC: R-11, R-12, R-113, R-114, R-502

 

HFC: R-404a (HP62), R-407a, R-407c (AC9000), R-134a, R-410a (AZ20),

 

R-507 (AZ50), R-508b (SUVA95)

 

HCFC: R-22, R-23, R-123, R-124, R-401a (MP39), R-402a (HP80),

 

R-402b (HP81), R-408a, R-409a, R-500, R-503

 

HALON: 1301

Coverage

Single zone

Measuring Range

All gases 0 to 1,000 ppm

Monitoring Distance

Up to 50 ft (15.2 m) maximum gas-sample line length

Front Panel

3 Indicator lights:

 

MONITOR ON – Green light ON when the unit is operating normally,

 

or flashing during warm-up

 

SYSTEM FAULT – Yellow light ON when there is a system fault

 

ALARM – Red light ON when the gas level is above an alarm setting

Alarms

Four SPDT relays are provided (rated 3 A, 240 VAC):

 

three assigned to ppm level alarms – one assigned to system faults

 

Internal audible alarm programmable for any of the following conditions: system

 

fault, leak alarm, spill alarm, evacuation alarm, monitoring stopped or off

Detector Type

Infrared, Non-Dispersive

Sensitivity

All gases 1 ppm

Accuracy

All gases ±10 ppm from 0 to 100 ppm

 

All gases ±10% of reading from 100 to 1,000 ppm

Response Time/Flow Rate... Dependent on gas-sample line length; 0.25" OD x 0.17" ID tubing:

 

 

Gas-Sample Line

 

Response Time

 

Flow Rate

 

 

 

Feet (Meters)

 

Seconds

 

ml/min

 

 

 

0

(0)

 

9

 

675

 

 

 

10

(3.0)

 

13

 

664

 

 

 

20

(6.1)

 

17

 

653

 

 

 

30

(9.1)

 

22

 

642

 

 

 

40

(12.2)

 

26

 

631

 

 

 

50

(15.2)

 

30

 

620

 

Temperature Drift

±0.8% (R-134a) of reading per °C

 

 

System Noise

Less than 40dB(A) at 10 ft (3 m)

 

 

Conditioned Signal

4–20 mA current loop

 

 

 

 

Power Safety Mode

Fully automatic system reset; all programmed parameters retained

Operating Temp

32 to 122°F (0 to 50°C)

 

 

 

 

Ambient Humidity

5% to 90% RH (non-condensing)

 

 

Altitude Limit

6,562 ft (2,000 m)

 

 

 

 

AC Power

100 – 240 VAC

 

 

 

 

Power Consumption

15 Watts

 

 

 

 

 

 

Size/Weight

7.4"H x 15"W x 3.3"D / 5 lbs (188 x 381 x 84 mm / 2.27 kg)

Certification

UL 61010A-1, CAN/CSA 22.2 No. 1010-1B:1997,

 

CE Mark (see inside front cover), UL 2075

 

 

Warranty

2 Years from date of shipment

 

 

30

Instruction 3015-4256

Page 34
Image 34
Bacharach 3015-4256 manual Specifications, Halon