Tubing Considerations
¼" outside diameter (0.040" wall) flex tubing is used for all air lines (P/N
Connecting the Gas-Sample Line
To connect the
Please refer to Section Suggested Location of Sampling Point (Page 4) to learn more about where to take a sample.
The
CAUTION: The introduction of contaminants through the
Connecting the Exhaust Line
The exhaust line functions to carry the exhausted gas sample away from the monitor, and is required if the monitor is located in a confined, poorly ventilated area. Note that if the monitor is exposed to usually high level of refrigerant gas for prolonged periods of time, its charcoal filter will quickly become saturated and no longer to able to clean the
The exhaust line can be up to 50 ft (15.2 m) in length. Ideally this line should terminate outdoors in a location that is not exposed to the elements. Connect the exhaust line to the monitor by firmly pushing the tubing onto the Exhaust Port’s barbed fitting. If the exhaust line terminates outside the building, position the tubing so that no water or moisture can enter the line. Note that this line does not require a termination filter.
Termination Filter
Instruction | 7 |