Electrical Connections All load connections are made at the panel using electrical cords with the proper mating plug for the receptacle being used. More than one receptacle can be used as long as the total load does not exceed the continuous rating of the generator.

WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician has installed an approved transfer switch. The National Electrical Code (NEC) requires that connection of a generator to any electrical circuit normally powered by means of an electric utility must be connected by means of approved transfer switch equipment so as to isolate the electrical circuit from the utility distribution system when the generator is operating. Failure to isolate the electrical circuits by such means may result in injury or death to utility power workers due to backfeed of electrical energy onto the utility lines.

Use correct size insulated wire to connect the generator to the load. The gauge of the wire will depend on the distance to the load, the permissible voltage drop at the load, and the current required by the load. If you are not sure of the gauge wire needed for your application, consult a competent electrician. Using wire that is too small can result in fire hazard. Also, be sure the wire has the appropriate ratings for insulation and environment conditions.

The correct mating connector must be used to fit the connectors provided on the operator panel of your generator. Table 3-1describes the connector types provided (receptacles) and the load characteristics to help you choose the correct size wire. Figure 3-2shows the receptacles.

Table 3-1 Single Phase Power Receptacle Description

Model

 

Electrical Connection Information (Receptacle Provided at Panel)

 

 

 

 

 

 

 

 

Straight 120VAC

 

Twist Lock 120/240VAC

 

Rated Watts/

 

(20Amp)

 

(30Amp)

 

(Full load Amps 120/240)

 

 

 

 

 

 

PG6000

2− 520R 120VAC

 

1− L1430R 120/240VAC

 

5700 / (44.2/22.1)

Class 1 wiring methods must be used for field wiring connections to terminals of a Class 2 circuit.

Figure 3-2 Receptacle Connections

Ground

 

(GOLD)

120VAC

G

X

 

 

NEMA

L14−30R

125/250V

30A

NEMA 520R

120VAC

Y

W

Neutral

(GOLD)

(SILVER)

125V 20A

 

 

 

 

 

 

MN2418

Receiving & Installation 3-3

Page 15
Image 15
Baldor PG 6000 manual Single Phase Power Receptacle Description, Receptacle Connections