Bard CH4S1, CH5S1 Table Pressure Table, Manual, 2100-455A, Page, 24 of, High Capacity Cooling

Models: CH3S1 CH5S1 CH4S1

1 25
Download 25 pages 23.1 Kb
Page 24
Image 24
TABLE 10

TABLE 10

PRESSURE TABLE

HIGH CAPACITY COOLING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

RETURN AIR

PRESSURE

75oF

80oF

85oF

90oF

95oF

100oF

105oF

110oF

115oF

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

75° DB

LOW SIDE

134

134

134

135

137

138

140

143

146

 

62° WB

HIGH SIDE

298

318

339

363

388

415

445

476

510

CH3S1

80° DB

LOW SIDE

143

143

143

144

146

148

150

153

156

67° WB

HIGH SIDE

306

326

348

372

398

426

456

488

523

 

 

85° DB

LOW SIDE

148

148

148

149

151

153

155

158

161

 

72° WB

HIGH SIDE

317

337

360

385

412

441

472

505

541

 

75° DB

LOW SIDE

131

133

135

137

138

139

139

140

140

 

62° WB

HIGH SIDE

308

332

356

380

406

431

456

483

509

CH4S1

80° DB

LOW SIDE

140

142

144

146

148

149

149

150

150

67° WB

HIGH SIDE

316

340

365

390

416

442

468

495

522

 

 

85° DB

LOW SIDE

145

147

149

151

153

154

154

155

155

 

72° WB

HIGH SIDE

327

352

378

404

431

457

484

512

540

 

75° DB

LOW SIDE

130

131

131

132

134

135

137

138

140

 

62° WB

HIGH SIDE

336

359

381

406

430

455

482

510

538

CH5S1

80° DB

LOW SIDE

139

140

140

141

143

144

146

148

150

67° WB

HIGH SIDE

345

368

391

416

441

467

494

523

552

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85° DB

LOW SIDE

144

145

145

146

148

149

151

153

155

 

72° WB

HIGH SIDE

357

381

405

431

456

483

511

541

571

Low side pressure ± 2 PSIG High side pressure ± 5 PSIG

Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instruction.

TABLE 11

PRESSURE TABLE

LOW CAPACITY COOLING

AIR TEMPERATURE ENTERING OUTDOOR COIL DEGREE F

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

RETURN AIR

PRESSURE

75oF

80oF

85oF

90oF

95oF

100oF

105oF

110oF

115oF

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

75° DB

LOW SIDE

139

140

141

142

143

145

147

149

151

 

62° WB

HIGH SIDE

259

284

308

333

359

385

410

438

464

CH3S1

80° DB

LOW SIDE

149

150

151

152

153

155

157

159

161

67° WB

HIGH SIDE

266

291

316

342

368

395

421

449

476

 

 

85° DB

LOW SIDE

154

155

156

157

158

160

162

165

167

 

72° WB

HIGH SIDE

275

301

327

354

381

409

436

465

493

 

 

 

 

 

 

 

 

 

 

 

 

 

75° DB

LOW SIDE

137

137

139

140

141

143

144

146

147

 

62° WB

HIGH SIDE

281

301

323

345

370

394

419

447

475

CH4S1

80° DB

LOW SIDE

146

147

149

150

151

153

154

156

157

67° WB

HIGH SIDE

288

309

331

354

379

404

430

458

487

 

 

85° DB

LOW SIDE

151

152

154

155

156

158

159

161

162

 

72° WB

HIGH SIDE

298

320

343

366

392

418

445

474

504

 

75° DB

LOW SIDE

136

137

139

141

142

143

144

145

145

 

62° WB

HIGH SIDE

293

316

340

364

389

413

439

464

489

CH5S1

80° DB

LOW SIDE

145

147

149

151

152

153

154

155

155

67° WB

HIGH SIDE

300

324

349

373

399

424

450

476

502

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85° DB

LOW SIDE

150

152

154

156

157

158

159

160

160

 

72° WB

HIGH SIDE

311

335

361

386

413

439

466

493

520

Low side pressure ± 2 PSIG High side pressure ± 5 PSIG

Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instruction.

Manual

2100-455A

Page

24 of 25

Page 24
Image 24
Bard CH4S1, CH5S1, CH3S1 Table Pressure Table, Manual, 2100-455A, Page, 24 of, High Capacity Cooling, Low Capacity Cooling