TABLE 12

PRESSURE TABLE

HIGH CAPACITY HEATING

 

 

 

 

AIR TEMPERATURE ENTERING OUTDOOR COIL DEGREE F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

RETURN AIR

PRESSURE

0oF

5oF

10oF

15oF

20oF

25oF

30oF

35oF

40oF

45oF

50oF

55oF

60oF

65oF

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CH3S

70°

LOW SIDE

44

46

50

54

59

64

71

78

86

95

105

116

127

139

HIGH SIDE

290

295

300

303

304

309

318

330

346

364

387

413

442

475

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CH4S

70°

LOW SIDE

54

55

56

56

57

61

66

74

83

94

108

123

141

160

HIGH SIDE

280

281

283

284

288

294

304

317

334

353

376

402

431

463

 

 

CH5S

70°

LOW SIDE

44

46

49

53

57

63

68

75

82

90

99

108

119

129

HIGH SIDE

272

277

284

293

304

316

330

346

364

383

404

427

452

478

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low side pressure ± 2 PSIG High side pressure ± 5 PSIG

Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instruction.

TABLE 13

PRESSURE TABLE

LOW CAPACITY HEATING

 

 

 

 

AIR TEMPERATURE ENTERING OUTDOOR COIL DEGREE F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

RETURN AIR

PRESSURE

0oF

5oF

10oF

15oF

20oF

25oF

30oF

35oF

40oF

45oF

50oF

55oF

60oF

65oF

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CH3S

70°

LOW SIDE

46

49

53

57

62

68

75

83

91

101

111

122

134

146

HIGH SIDE

275

280

283

283

286

291

298

308

320

334

350

369

389

412

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CH4S

70°

LOW SIDE

60

65

63

61

62

64

70

77

87

99

113

130

149

170

HIGH SIDE

270

271

271

273

278

284

293

303

316

331

348

367

388

411

 

 

CH5S

70°

LOW SIDE

58

56

56

58

60

64

70

77

85

95

106

119

133

148

HIGH SIDE

275

274

275

279

285

294

306

321

338

358

381

406

434

465

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low side pressure ± 2 PSIG High side pressure ± 5 PSIG

Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instruction.