Bard CH3S1 installation instructions CH4S1, CH5S1

Models: CH3S1 CH5S1 CH4S1

1 25
Download 25 pages 23.1 Kb
Page 23
Image 23
CH3S1

TABLE 7 1

REFRIGERANT CHARGE - SUBCOOLING LEVEL

 

 

COOLING

HEATING

 

 

 

 

 

 

 

Rated

95 OD

80 OD

47 OD

35 OD

Model

Airflow

Temperature

Temperature

Temperature

Temperature

 

 

 

 

 

 

CH3S1

1100

16 - 20

15 - 19

28 - 32

26 - 30

 

 

 

 

 

 

CH4S1

1500

18 - 22

17 - 21

20 - 24

15 - 19

 

 

 

 

 

 

CH5S1

1700

26 - 30

20 - 24

31 - 35

27 - 31

 

 

 

 

 

 

1 Expected subcooling levels during high capacity Stage 2 operation. Above subcooling levels are provided to troubleshoot low charge or overcharged conditions. If charge is in doubt, evacuate and recharge the unit to the refrigerant charge listed on the serial plate.

TABLE 8

INDOOR BLOWER PERFORMANCE

 

Rated

1

2

3

4

 

Model

Max

2nd Stage Cooling

1st Stage Cooling

Blower Only

Electric Heat

ESP

 

ESP

2nd Stage Heating

1st Stage Heating

or Vent Mode

 

 

 

 

 

 

 

 

 

 

 

CH3S1

.15

.5

1100

800

800

1100

 

 

 

 

 

 

 

CH4S1

.2

.5

1500

1100

850

1700

 

 

 

 

 

 

 

CH5S1

.2

.5

1700

1300

850

1700

 

 

 

 

 

 

 

NOTE: These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintain approximately the same rate of indoor airflow in both heating and cooling, dry and wet coil conditions and at both 230/ 208 or 460 volts.

1 Maximum ESP (inches WC) shown is with 2" thick disposable filter.

2 Rated CFM for 2nd Stage Operation – required for maximum performance rating.

3 1st Stage – the CFM output on 1st Stage Heating or Cooling.

4 Blower only CFM is the total air being circulated during continuous fan mode.

TABLE 9

MAXIMUM ESP OF OPERATION

High Speed

ALL

.5

Manual

2100-455A

Page

23 of 25

Page 23
Image 23
Bard CH3S1 installation instructions CH4S1, CH5S1