DEFROST CYCLE

The defrost cycle is controlled by temperature and time on the solid state heat pump control. See Figure 12.

When the outdoor temperature is in the lower 40° F temperature range or colder, the outdoor coil temperature is 32° F or below. This coil temperature is sensed by the coil temperature sensor mounted near the bottom of the outdoor coil. Once coil temperature reaches 30° F or below, the coil temperature sensor sends a signal to the control logic of the heat pump control and the defrost timer will start.

After 60 minutes at 30° F or below, the heat pump control will place the system in the defrost mode.

During the defrost mode, the refrigerant cycle switches back to the cooling cycle, the outdoor motor stops, electric heaters are energized, and hot gas passing through the outdoor coil melts any accumulated frost. When the temperature rises to approximately 57° F, the coil temperature sensor will send a signal to the heat pump control which will return the system to heating operations automatically.

If some abnormal or temporary condition such as a high wind causes the heat pump to have a prolonged defrost cycle, the heat pump control will restore the system to heating operation automatically after 10 minutes.

The heat pump defrost control board has an option of 30, 60 or 90-minute setting. All models are shipped from the factory on the 60-minute pin. If special circumstances require a change to another time, remove the wire from the 60-minute terminal and reconnect to the desired terminal. The manufacturer's recommendation is for 60-minute defrost cycles. Refer to Figure 12.

FIGURE 12

DEFROST CONTROL BOARD

There is a cycle speed up jumper on the control. This can be used to reduce the time between defrost cycle operation without waiting for time to elapse.

Use a small screwdriver or other metallic object, or another 1/4 inch QC, to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost.

Be careful not to touch any other terminals with the instrument used to short the SPEEDUP terminals. It may take up to 10 seconds with the SPEEDUP terminals shorted for the speedup to be completed and the defrost cycle to start.

As soon as the defrost cycle kicks in remove the shorting instrument from the SPEEDUP terminals. Otherwise the timing will remain accelerated and run through the 1-minute minimum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence.

There is an initiate defrost jumper (sen jump) on the control that can be used at any outdoor ambient during the heating cycle to simulate a 0° coil temperature. This can be used to check defrost operation of the unit without waiting for the outdoor ambient to fall into the defrost region.

By placing a jumper across the SEN JMP terminals (a 1/4 inch QC terminal works best) the defrost sensor mounted on the outdoor coil is shunted out and will activate the timing circuit. This permits the defrost cycle to be checked out in warmer weather conditions without the outdoor temperature having to fall into the defrost region.

In order to terminate the defrost test the SEN JMP jumper must be removed. If left in place too long the compressor could stop due to the high pressure control opening because of high pressure condition created by

operating in the cooling mode with outdoor fan off. Pressure will rise fairly fast as there is likely no actual frost on the outdoor coil in this artificial test condition.

There is also a 5-minute compressor time delay function built into the HPC. This is to protect the compressor from short cycling conditions. In some instances, it is helpful to the service technician to override or speed up this timing period, and shorting out the SPEEDUP terminals for a few seconds can do this.

Manual

2100-455A

Page

19 of 25

Page 19
Image 19
Bard CH5S1, CH4S1, CH3S1 installation instructions Defrost Cycle, Defrost Control Board

CH3S1, CH5S1, CH4S1 specifications

Bard CH3S1, CH4S1, and CH5S1 represent a formidable trio of advanced technologies in the field of AI-driven natural language processing. These models are designed to facilitate seamless communication, enhance productivity, and deliver personalized experiences across various applications.

One of the main features of the Bard CH series is its ability to understand and generate human-like text. This is achieved through deep learning algorithms that analyze vast datasets to learn language patterns, context, and nuances. The CH3S1 model, for instance, excels in basic conversational tasks, making it suitable for customer support, virtual assistants, and simple content generation. Its training allows it to respond efficiently to user inputs while maintaining clarity and engagement.

As we progress to the CH4S1 model, we observe significant enhancements in contextual understanding. This model can handle more complex conversations, making it adept at tasks requiring greater cognitive processing, such as technical support and nuanced dialogue-based applications. The increased parameter count and refined training methods contribute to its ability to grasp intricate sentence structures and varied linguistic styles, leading to more coherent and relevant responses.

Building upon the capabilities of its predecessors, the CH5S1 model represents the pinnacle of the Bard CH series. It integrates advanced features such as multi-modal processing, allowing it to work with text, images, and even sound. This model is engineered to perform in more specialized fields, such as healthcare, legal, and creative writing, where precise language and context are critical. The CH5S1 leverages feedback loops from real-time interactions to continuously improve its understanding and output, making it not only a tool for communication but also an intelligent partner for businesses and individuals alike.

In terms of technology, all three models utilize transformer architecture, which has proven effective in tasks requiring attention and context retention. They also implement reinforcement learning techniques to adapt and refine their models based on user engagement data. Furthermore, security and data privacy are prioritized, with strict adherence to ethical AI guidelines to ensure user trust.

Overall, the Bard CH series signifies a leap forward in artificial intelligence, combining advanced linguistic capabilities with a user-centric approach, thus redefining how we interact with machines and enhancing our digital experiences.