WIRING – MAIN POWER

FIGURE 9

COMMON WALL MOUNTING INSTALLATIONS

Closet Installation

Note: duct maybe in attic or below rafters as shown.

Rafters

 

Unit (outside)

 

Supply Air

Duct

Finished Ceiling

Grille

Wall Sleeve

 

Outside Wall

Return Air

Closet Wall

Closet Wall

 

 

Raised Closet Floor

Grille

 

 

Return Air

 

MIS-2240

WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75° C copper) for all models including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry.

See “Start Up” section for important information on three phase scroll compressor start ups.

WIRING – LOW VOLTAGE WIRING

230 / 208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

FIGURE 10

UNIT 24V TERMINAL BOARD

 

 

 

 

 

 

T7652H1000 THERMOSTAT

 

 

 

 

 

 

 

BARD PART #8403-052

C

G

Rc Rh

Y1

Y2

B

W1

 

L

A1

 

 

 

 

 

 

 

1F93-380 THERMOSTAT

 

 

 

 

 

 

 

BARD PART #8403-049

C

G

R

Y1

Y2

B

W1

W2

E

W3/A1

C

G

R

Y

Y1

B

W1 W2

W3

E L

DH O1

 

 

 

Factory Jumper

 

 

UNIT LOW VOLTAGE

 

 

 

 

 

TERMINAL BLOCK

MIS-2026 A

Nine (9) wires should be run from thermostat subbase to the 24V terminal board in the unit. A nine conductor, 18 gauge copper color-coded thermostat cable is recommended. The connection points are shown in Figure 10.

IMPORTANT

Only the thermostat combinations as shown above will work with this equipment.

TABLE 3

THERMOSTAT WIRE SIZE

 

 

 

Maximum

Transformer

 

 

Distance

VA

FLA

Wire Gauge

In Feet

 

 

 

 

 

 

20 gauge

45

 

 

18 gauge

60

55

2.3

16 gauge

100

 

 

14 guage

160

 

 

12 guage

250

 

 

 

 