MC4000Series
Solid State Dual Unit LeadLag Controller
Alarms
Alarm boards are optional and can be factory or field installed. See inside of controller for any alarm functions.
Power Loss Sys. 1
Power Loss Sys. 2
Refrig. Alarm Sys. 1
Refrig. Alarm Sys. 2
Fire/Smoke AlarmLow Temp. Alarm
High Temp. Alarm 1
High Temp. Alarm 2Lead/Lag Controller
Failure Alarm1st | 2nd | 3rd | 4th | Cooling | |
Stage | Stage | Stage | Stage | ||
| |||||
1st | 2nd | 3rd | 4th | Heating | |
Stage | Stage | Stage | Stage | ||
|
|
|
| Digital | |
|
|
|
| Display | |
Lead | Unit | Unit |
| Dehumid. | |
Unit | #1 | #2 |
| Operation |
On
Off
Program
Advance
ChangeComfort
Save
Operating Instructions
1.To swap lead and lag units press “ADVANCE”.2.To enter the Program mode press the “Program” button and release it when “Pro9” appears. Use “DOWN” or “UP” arrows to scroll through menu.
3.A “Flashing” display means that the function or choice is “Set”, and the display will alternate between the step function and setting.
4.To change the setting of any step press the “Change” button and the display will stop flashing, allowing change to the setting by using the “Down” or “Up” arrows. When desired setting is reached press the “Save” button, and proceed as desired.
5.When done programming press the “Program” button until display stops flashing and room temperature is shown. If no buttons are pushed within
Comfort Mode
Press “Comfort” button once to reset to 72F/22C Cooling and 68F/20C Heating for
Program Menu
NOTE: Push and hold Up or Down arrows for
until display blanks to move between steps.
1 Temperature at local (main) Sensor
2 Temperature at Remote 1 sensor location*
3 Temperature at Remote 2 sensor location*
4 Cooling setpoint temperature
(65 to 90F or 18.3 to 32.2C - Default is 77F/25C)
5 Deadband between cooling and heating setpoint (2 to 40F or 1.1 to 22.2C - Default is 17F/9.4C)
6 Continuous blower operation
(None, Lead, Both - Default is None)
7 | Degree display (F or C - Default is F) |
8 Alternating
9
(1 to 30 days, or 0 for disabled - Default is 7)
10 Heat pump logic enabled - only for
(Yes or No - Default is No)
11 Unit 1 and 2 blowers automatically both run if delta T>5F between any 2 connected sensors (Yes or No - Default is Yes)
12 | (Yes or No - Default is No) | |||
|
|
| ||
13 | Minimum of | (Yes or No - Default is No) | ||
|
|
| ||
14 | Low temperature alarm setpoint | (28 to 65F or 21.1 to 48.8C - Default is 45F/7.2C) | ||
|
|
|
|
|
15 | High temperature alarm Level 1 setpoint |
|
|
|
| (70F to 120F or 21.1 to 48.8C - Default is 90F/32.2C) |
|
| |
|
|
| ||
16 | High temperature alarm Level 2 setpoint | (70F to 120F or 21.1 to 49C - Default is 95F/35C) | ||
|
|
|
| |
17 |
| (2, 3, 4, 5 or 6F - Default is 4) | ||
|
|
|
|
|
18 |
|
| (2 or 3F - Default is 2) | |
|
|
|
| |
19 |
| (2 or 3F - Default is 2) | ||
|
|
|
|
|
20 | Turn “On” above SP for Stage 1 Cooling |
|
| (+1 or +2 - Default is +2) |
|
|
|
| |
21 | Turn “Off” below SP for Stage 1 Cooling |
| ||
| Note: For CSon and CSoF Stage 2, 3 and 4 Cooling are automatically same as Stage 1 | |||
|
|
| ||
22 | All Heating stages are equal | |||
|
| |||
23 | 1 or | |||
| If set to 2 the | (1 or 2 - Default is 1) |
24 Controller is Locked. Consult building authority for further instructions.
*r1 and r2 will display temperature only if optional remote sensors are installed.
If sensors are not installed these are omitted in the display sequence. If r1 and/or r2 sensor installed the MC4000 will control to the “average” of the connected sensors.
Consult installation instructions for additional details.