6.
1st stage cooling set point is the setting (SP) input into the controller. Factory default is 77F (25C). On a call for cooling the blower of the lead unit will come on immediately (if not already on – See Blower Operation), and the Stage 1 LED will blink for 10- seconds before going solid, at which time the lead unit Y1 cooling output turns on. If the outdoor temperature and humidity conditions are below the set point of the economizer control the lead unit economizer will operate instead of the compressor. If outdoor conditions are not acceptable for free cooling the compressor will automatically operate on compressor Stage 1 partial capacity instead of the economizer.
2nd cooling set point is 4F (default setting, user selectable
3rd cooling set point is 2F (default setting, user selectable
4th cooling set point is 2F (default setting, user selectable
COOLING OPERATING SEQUENCES FOR
Note: Heat pumps cannot be operated in
1.2-Stage Compressor Units No Economizer
1st stage1st stage cooling set point is the setting (SP) input into the controller. Factory default is 77F (25C). On a call for cooling the blower of the lead unit will come on immediately (if not already on – See Blower Operation), and the Stage 1 LED will blink for 10- seconds before going solid, at which time the lead unit compressor will start in compressor Stage 1 partial capacity operation.
2nd cooling set point is 4F (default setting, user selectable
3rd cooling set point is 2F (default setting, user selectable
4th cooling set point is 2F (default setting, user selectable
2.
1st stage cooling set point is the setting (SP) input into the controller. Factory default is 77F (25C). On a call for cooling the blower of the lead unit will come on immediately (if not already on – See Blower Operation), and the Stage 1 LED will blink for
2nd cooling set point is 4F (default setting, user selectable
Manual | |