HUMIDITY CONTROL OPTION
Note: This function is not available if controller is configured for heat pump.
The standard air conditioning system can be adapted to perform dehumidification control by addition of a simple humidity controller that
1.Temperature control always has priority over dehumidification. If there is any stage of cooling demand active, the dehumidification sequence is locked out.
2.If all stages of cooling are satisfied, and relative humidity is above the set point of humidity controller:
a.The green “Dehumid. Operation” light will come on, and the lag unit compressor and blower will operate until the set point of humidity controller is satisfied (or cancelled by a call for cooling).
b.If the space temperature drops to 67F, the electric heater of the lead unit will cycle to help maintain building temperature. It will cycle off at 69F.
c.If space temperature drops to 64F, the Stage 2 Heating light will come on and the lag unit compressor operating for dehumidification mode will cycle off until the building temperature rises above 65F from 1st stage heat and building load. The green “Dehumid. Operation” light stays on during this sequence, and when Stage 2 Heating light is Off, the compressor is On. The electric heater in lag unit is locked out in dehumidification mode.
Lag unit outputs G, Y1 and Y2 are all switched on during dehumidification sequence. This is true for both alternating and
CAUTION
Humidity controller set point should be in
COOLING OPERATING SEQUENCES FOR ALTERNATING LEAD/LAG/LEAD/LAG CONFIGURATION
1.
1st stage cooling set point is the setting (SP) input into the controller. Factory default is 77F (25C). On a call for cooling the blower of the lead unit will come on immediately (if not already on – See Blower Operation), and the Stage 1 LED will blink for
2nd cooling set point is 4F (default setting, user selectable
3rd and 4th stages are functional outputs but there is nothing to be controlled.
2.
1st stage cooling set point is the setting (SP) input into the controller. Factory default is 77F (25C). On a call for cooling the blower of the lead unit will come on immediately (if not already on – See Blower Operation), and the Stage 1 LED will blink for
2nd cooling set point is 4F (default setting, user selectable
3rd cooling set point is 2F (default setting, user selectable