LOW VOLTAGE FIELD WIRING
The MC4000 is powered from the air conditioners that it is controlling, 24 VAC
Circuitry in the MC4000 isolates the power supplies of the two air conditioners so that no back feeds or phasing problems can occur. Additionally, if one air conditioner loses power, the MC4000 and the other air conditioner are unaffected and will continue to operate normally.
Connect the low voltage field wiring from each unit per the low voltage field wiring diagrams in Section on “Controller Wiring”. NOTE: Maximum of
CONTROLLER GROUNDING
A reliable earth ground must be connected in addition to any grounding from conduit. Grounding lugs are supplied for this purpose.
CONTROLLER POWER-UP
Whenever power is first applied to the controller, there is a twenty (20) second
FIRE SUPPRESSION CIRCUIT
To disable the MC4000 and shut down both air conditioners, terminals F1 and F2 may be used. The F1 and F2 terminals must be jumpered together for normal operation. A normally closed (nc) set of dry contacts may be connected across the terminals and the factory jumper removed for use with a
IMPORTANT NOTE: Older Bard
control to the “R” terminal on the blower control. The electronic blower control will now function as an
STAGING DELAY PERIODS
The following delays are built in for both cooling & heating:
Stage 1 – 0 seconds for blower (if not already on as continuous)
10 seconds for cooling or heating output
Stage 2 – 10 seconds after Stage 1 for blower
10 additional seconds for cooling or heating output
Stage 3 – 10 seconds after Stage 2
Stage 4 – 10 seconds after Stage 3
Note: For cooling Stages 1 and 2, the stage LED will blink for 10 seconds while the cooling output is delayed after that stage is called for. There is also a delay after the stage is satisfied, and after the LED stops blinking, the stage will turn off. There is a minimum
BLOWER OPERATION
The controller can be configured to have main HVAC blowers cycle on and off on demand; have all blowers run continuously; or have the lead unit blower run continuously with the lag unit blower cycling on demand. Default setting is the blower(s) start and stop on demand. There is also an option to have all blowers cycle on if one remote sensor is connected, and a temperature difference of more than 5F between any two sensors is observed. This helps to redistribute the heat load within the structure and should reduce compressor operating time.
When any of the stages are satisfied, the stage LED will blink for ten (10) seconds before the stage is actually turned off.
ADVANCE (SWAP) LEAD/LAG UNIT FEATURE
Pressing the Advance button for one (1) second will cause the lead and lag units to change positions. This may be useful during service and maintenance procedures.
ACCELERATE TIMER FEATURE
Pressing the UP arrow button for five (5) seconds will activate an accelerate
Manual | |
Page | 7 of 40 |