BASIC MC4000 CONTROLLER INPUT/OUTPUT SPECIFICATIONS
MC4000 CONTROLLER CONNECTIONS
Located on Main Controller Board
Unit #1 | C – 24VAC common |
| |
| R – 24VAC hot |
| |
| G – fan (Form A, NO) |
| |
| Y1 – | ||
| Y2 – | ||
| W – heat (Form A, NO) |
| |
Unit #2 | C – 24VAC common |
| |
| R – 24VAC hot |
| |
| G – fan (Form A, NO) |
| |
| Y1 – | ||
| Y2 – | ||
| W – heat (Form A, NO) |
| |
Fire/smoke interface |
| ||
| Shipped with jumper installed (a) |
| |
48Vdc |
| ||
|
| ||
|
| ||
| NOTE: | ||
Local | Main sensor, | ||
| |||
| CU – copper, AG – silver | Sensors are | |
| Polarity sensitive | solid state, | |
Rem 1 | Optional remote indoor sensor | not RTD. | |
| CU – copper, AG – silver | ||
| Use Bard | ||
| Polarity sensitive | ||
|
| ||
Rem 2 | Optional remote indoor sensor | sensors only. | |
| CU – copper, AG – silver |
| |
|
| ||
| Polarity sensitive |
| |
Gen | Generator interface |
| |
| Shipped with jumper installed (a) |
| |
Humidity controller input |
| ||
| Requires optional controller |
| |
| Field installed |
|
(a)These connections require either jumper or Normally Closed (NC) relay contact at the Fire/Smoke and Generator interface for Controller to function.
Note: All alarm and output relays are dry contacts rated 1A @ 24 VAC.
Note: All alarm relay outputs have
SPECIFICATIONS/FEATURES FOR ALARM BOARDS
NOTE: If this alarm board was not originally factory installed, it can be
Inputs |
|
Lockout 1 | 2,3 – input from HVAC #1 |
Lockout 2 | 2, 3 – input from HVAC #2 |
Outputs |
|
Smoke/Fire | Form C (SPDT) |
Lockout 1 | Form C (SPDT) |
| Refrigerant alarm HVAC #1 |
Lockout 2 | Form C (SPDT) |
| Refrigerant alarm HVAC #2 |
Power Loss 1 | Form C (SPDT) |
| Power loss HVAC #1 |
Power Loss 2 | Form C (SPDT) |
| Power loss HVAC #2 |
Low Temp | Form C (SPDT) |
| Low temperature alarm |
High Temp 1 | Form C (SPDT) |
| High temperature alarm #1 |
NOTE: If this alarm board was not originally factory installed, it can be
High Temp 2 | Form C (SPDT) |
| High temperature alarm #2 |
Controller | Form C (SPDT) |
| Controller failure alarm |
Econ 1 | E, F - Form A (NO) |
| See note (b) |
Econ 2 | E, F - Form A (NO) |
| See note (b) |
2nd Stage (c) | Form C (SPDT) |
|
(b)Make these connections to terminals E & F in HVAC 1 and 2 respectively if desired to have economizers open for emergency ventilation at High Temp Alarm #2 setpoint condition.
(c)For units with
Alarm relays can be wired for NO (close on alarm) or NC (open on alarm) strategy. Alarm relays can be used individually if there are enough available building alarm points, or can be arranged into smaller groups or even a single group so that all alarm capabilities can be utilized. When multiple alarms are grouped together and issued as a single alarm there will be no
Manual | |
Page | 6 of 40 |