TABLE 7

TABLE 7

COOLING PRESSURE

(ALL TEMPERATURES IN DEGREES F)

 

RETURN

 

 

AIR TEMPERATURE ENTERING OUTDOOR COIL

 

 

AIR

 

 

 

 

 

 

 

 

 

 

 

 

 

75

80

85

90

95

100

105

110

 

115

MODEL

TEMP.

PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

116

119

122

124

127

130

132

134

 

136

 

62 WB

High Side

314

335

358

380

404

428

452

478

 

503

 

 

 

 

 

 

 

 

 

 

 

 

 

Q24A1

80 DB

Low Side

124

127

130

133

134

139

141

143

 

145

67 WB

High Side

322

344

367

390

414

439

464

490

 

516

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

128

131

135

138

141

144

146

148

 

150

 

72 WB

High Side

333

356

380

404

428

454

480

507

 

534

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

119

121

122

124

127

129

131

133

 

135

 

62 WB

High Side

321

344

368

391

414

437

460

484

 

507

 

 

 

 

 

 

 

 

 

 

 

 

 

Q30A1

80 DB

Low Side

127

129

131

133

136

138

140

142

 

144

67 WB

High Side

329

353

377

401

425

448

472

496

 

520

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

131

134

136

138

141

143

145

147

 

149

 

72 WB

High Side

341

365

390

415

440

464

489

513

 

538

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

112

118

123

128

132

136

137

139

 

140

 

62 WB

High Side

347

373

401

428

454

481

508

534

 

561

 

 

 

 

 

 

 

 

 

 

 

 

 

Q36A1

80 DB

Low Side

120

126

132

137

141

145

147

149

 

150

67 WB

High Side

356

383

411

439

440

493

521

548

 

575

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

124

130

137

142

146

150

152

154

 

155

 

72 WB

High Side

368

396

425

454

482

510

539

567

 

595

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

116

119

122

124

127

129

131

133

 

135

 

62 WB

High Side

356

380

406

431

457

483

509

535

 

563

 

 

 

 

 

 

 

 

 

 

 

 

 

Q42A1

80 DB

Low Side

124

127

130

133

136

138

140

142

 

144

67 WB

High Side

365

390

416

442

469

495

522

549

 

577

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

128

131

135

138

141

143

145

147

 

149

 

72 WB

High Side

378

404

431

457

485

512

540

568

 

597

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

119

121

122

124

127

129

131

134

 

136

 

62 WB

High Side

343

366

390

414

440

466

493

522

 

551

 

 

 

 

 

 

 

 

 

 

 

 

 

Q48A1

80 DB

Low Side

127

129

131

133

135

138

140

143

 

145

67 WB

High Side

352

375

400

425

450

478

506

535

 

565

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

131

134

136

138

141

143

145

148

 

150

 

72 WB

High Side

364

388

414

440

467

495

524

554

 

585

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

112

116

120

122

124

125

126

126

 

125

 

62 WB

High Side

362

386

410

436

462

488

514

541

 

568

 

 

 

 

 

 

 

 

 

 

 

 

 

Q60A1

80 DB

Low Side

120

124

128

130

131

134

135

135

 

134

67 WB

High Side

371

396

421

447

474

500

527

555

 

583

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

124

128

132

135

138

139

140

140

 

139

 

72 WB

High Side

384

410

436

463

491

518

545

574

 

603

 

 

 

 

 

 

 

 

 

 

 

 

 

Low side pressure ± 4 psig