All three phase scroll compressors used in the Q-TECseries are wired identically internally. As a result, once the correct phasing is determined for a specific system or installation, connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction. The direction of rotation of the motor may be changed by reversing any two line connections to the unit.

COMPRESSOR CONTROL MODULE

The compressor control module is standard on all models covered by this manual. The compressor control is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm relay output.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to the unit, the delay on make period begins, which will be 2 minutes plus 10% of the delay on break setting.

When the delay on make is complete and the high pressure switch (and low pressure switch if employed) is closed, the compressor contactor is energized.

Upon shutdown the delay or break timer starts and prevents restart until the delay on break and delay on make periods have expired.

During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on break time has expired. If the high pressure switch opens again in this same operating cycle the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

Low Pressure Switch, Bypass, and Lockout

Sequence

If the low pressure switch opens for more than 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will reenergize after the delay on make time delay has expired. If the low pressure switch remains open, or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications where alarm relay is employed. This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described.

NOTE: Both high and low pressure switch controls are inherently automatic reset devices. The high pressure switch and low pressure switch cut out and cut in settings are fixed by specific air conditioner or heat pump unit model. The lockout features, both soft and manual, are a function of the Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break Timer

The potentiometer is used to select Delay on Break time from 30 seconds to 5 minutes. Delay on Make (DOM) timing on power-up and after power interruptions is equal to 2 minutes plus 10% of Delay on Break (DOB)

setting:

 

 

0.5 minute (30 seconds)

DOB = 123

second DOM

1.0 minute (60 seconds)

DOB = 126

second DOM

2.0minute (120 seconds) DOB = 132 second DOM

3.0minute (180 seconds) DOB = 138 second DOM

4.0minute (240 seconds) DOB = 144 second DOM

5.0minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.

Typical Settings for Dual Unit Installation:

Unit 1: DOB set at 2 minutes, and DOM is 132 seconds

Unit 2: DOB set at 4 minutes, and DOM is 144 seconds

SERVICE HINTS

1.Caution user to maintain clean air filters at all times. Also, not to needlessly close off supply air registers. This may reduce airflow through the system, which shortens equipment service life as well as increasing operating costs and noise levels.

2.Check all power fuses or circuit breakers to be sure they are the correct rating.

3.Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.

Manual

2100-522B

Page

29 of 38

Page 29
Image 29
Bard Q48A1, Q30A1, Q36A1, Q42A1, Q60A1, Q24A1 installation instructions Compressor Control Module, Service Hints

Q48A1, Q24A1, Q60A1, Q42A1, Q36A1 specifications

The Bard Q60A1, Q48A1, Q30A1, Q36A1, and Q42A1 are innovative medical devices designed for versatile applications in various healthcare settings. These models are known for their adaptability, precision, and advanced technologies, making them essential tools for healthcare professionals.

The Q60A1 model stands out due to its user-friendly interface and high-resolution display. It is equipped with advanced sensors that provide real-time monitoring and feedback. The device's portability allows it to be easily moved between different areas of a facility, making it ideal for both inpatient and outpatient services. The Q60A1 also integrates seamlessly with electronic health records, enabling better data management and streamlined clinical workflows.

The Q48A1 model emphasizes flexibility and customization. With multiple configurations, this device is adept at accommodating a range of medical procedures. Its modular design allows healthcare providers to adjust the setup to meet their specific needs, enhancing both efficiency and patient comfort. The Q48A1 is favored for its rapid setup time, facilitating quick responses in critical situations.

In contrast, the Q30A1 prioritizes compactness without sacrificing functionality. This device is specifically engineered for smaller spaces, making it a perfect fit for clinics and smaller hospitals. Despite its size, the Q30A1 boasts a robust set of features, including wireless connectivity and the ability to store a significant amount of patient data. Its intuitive controls simplify operation, even for those with minimal training.

The Q36A1 model is notable for its durability and resilience in challenging environments. Constructed with high-grade materials, it withstands wear and tear while maintaining precise performance. The Q36A1 also includes advanced safety features, such as automatic shut-off mechanisms, which ensure safe operation in emergency conditions. Its reliability makes it a trusted choice across various healthcare sectors.

Lastly, the Q42A1 model focuses on user experience, combining technology with ease of use. It is equipped with voice-activated controls and touch-sensitive displays, streamlining interaction for medical staff. This model also features advanced data analytics tools, providing insights that can drive improvements in patient care.

Overall, the Bard Q60A1, Q48A1, Q30A1, Q36A1, and Q42A1 reflect the latest advancements in medical technology, each serving unique functions suited to different healthcare needs. These devices not only enhance operational efficiency but also improve patient outcomes through better monitoring and data management capabilities.