Bard WA423 A Indoor Blower Performance Cfm @, Table Recommended Airflow, Electric Heat Only

Models: WA423 WA381 WA484 WA491 WA602

1 21
Download 21 pages 18.9 Kb
Page 19
Image 19
TABLE 7A

TABLE 7A

INDOOR BLOWER PERFORMANCE

CFM @ 230V / 460V

 

 

 

WA381

 

 

 

WA491

 

 

 

 

 

 

 

 

 

 

 

 

E.S.P.

High Speed

Medium Speed

Low Speed

High Speed

Medium Speed

 

 

 

 

 

 

 

 

 

 

In

Dry

Wet

Dry

Wet

Dry

Wet

Dry

Wet

Dry

Wet

H2O

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

.0

1625

1475

1425

1325

1125

1100

1700

1550

1475

1375

.1

1475

1350

1325

1200

1100

1000

1550

1400

1375

1250

.2

1350

1150

1200

125

1000

850

1400

1250

1250

1100

.3

1150

825

1025

875

825

675

1250

1100

1100

825

.4

825

750

- - -

- - -

- - -

- - -

900

800

- - -

- - -

TABLE 8

RECOMMENDED AIRFLOW

 

Rated

Rated

Recommended

Factory Speed

Model

CFM *

ESP *

Airflow Range

Connection

 

 

 

 

 

WA381

1100

.15

1250 - 850

Medium

WA423

1400

.30

1600 - 1150

High

 

 

 

 

 

WA484

1550

.20

1750 - 1285

High

WA491

1250

.20

1475 - 1100

High

 

 

 

 

 

WA602

1700

.30

1950 - 1375

High

TABLE 9

MAXIMUM ESP OF OPERATION

ELECTRIC HEAT ONLY

Model

WA423

WA484

WA602

 

 

 

 

 

 

 

 

High

Low

High

Low

High

Low

KW

Speed

Speed

Speed

Speed

Speed

Speed

-A05

.50

.50

.50

.50

.50

.50

-A10

.50

.50

.50

.50

.50

.50

-A15

.50

.50

.50

.50

.50

.50

-A20

.50

.45

.50

.45

.50

.40

-B00

.50

.50

.50

.50

.50

.50

-B09

.50

.50

.50

.50

.50

.50

-B15

.50

.50

.50

.50

.50

.50

-B18

.50

.50

.50

.50

.50

.50

-C09

.50

.50

.50

.50

.50

.50

-C15

.50

.50

.50

.50

.50

.50

Values shown are for units equipped with standard 1 inch throwaway filter or 1 inch washable filter. Derate ESP by .15 for 2 inch pleated filters.

TABLE 9A

MAXIMUM ESP OF OPERATION

ELECTRIC HEAT ONLY

Model

 

WA381

 

WA491

 

 

 

 

 

 

 

High

Med

Low

High

Med

KW

Speed

Speed

Speed

Speed

Speed

-A05

.30

.30

.30

.30

.30

-A08

.30

.30

.30

.40

.40

-A10

.30

.30

.20

.30

.30

-B06

.40

.30

.30

.30

.30

-B09

.40

.30

.30

.30

.30

-C06

.30

.30

.30

.30

.30

-C09

.30

.30

.30

.30

.30

Values shown are for units equipped with standard 1 inch throwaway filter or 1 inch washable filter. Derate ESP by .15 for 2 inch pleated filters.

Manual 2100-398 Page 17

Page 19
Image 19
Bard WA423 A Indoor Blower Performance Cfm @, Table Recommended Airflow, Table Maximum Esp Of Operation Electric Heat Only