Bard WA423 Wiring - Main Power, Wiring - Low Voltage Wiring, Range, Table Thermostat Wire Size

Models: WA423 WA381 WA484 WA491 WA602

1 21
Download 21 pages 18.9 Kb
Page 14
Image 14

WIRING – MAIN POWER

WIRING – LOW VOLTAGE WIRING

Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring muse conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75° C copper) for all models including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

230 / 208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

Five (5) wires should be run from thermostat subbase to the 24V terminal board in the unit. A five conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 8:

The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability bend the tab located in the bottom left hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut a padlock may be placed through the hole in the tab preventing entry.

See “Start Up” section for important information on three phase scroll compressor start ups.

TABLE 3

THERMOSTAT WIRE SIZE

 

 

 

Maximum

Transformer

 

 

Distance

VA

FLA

Wire Gauge

In Feet

 

 

20 gauge

45

 

 

18 gauge

60

55

2.3

16 gauge

100

 

 

14 guage

160

 

 

12 guage

250

TABLE 4

WALL THERMOSTAT AND SUBBASE COMBINATIONS

 

Thermostat

Subbase

Predominate Features

 

 

 

 

 

 

 

8403-002

8404-003

1 stage heat, 1 stage cool

 

 

T87F3111

Q539A1220

System: heat-off-cool

Fan: auto-on

 

 

 

 

 

 

 

8403-041

---

1 stage heat, 1 stage cool

 

 

T8034C

 

System: heat-off-cool

Fan: auto-on

 

 

 

 

 

 

 

8403-019

8404-012

1 stage cool, 2 stage heat

 

 

T874C1760

Q674A1001

System: heat-auto-cool

Fan: auto-on

 

 

8403-021

8404-012

2 stage cool, 2 stage heat

 

 

T874D1934

Q674A1001

System: heat-auto-cool

Fan: auto-on

 

 

8403-049

---

2 stage cool, 2 stage heat

 

 

1F93-380

 

Electronic

7 day programming

 

 

8403-043

---

1 stage heat, 1 stage cool

 

 

CM-200

System: heat-off-cool

Fan: auto-on

 

 

 

 

 

8403-048

---

1 stage heat, 1 stage cool

 

 

T84001313

Electronic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual 2100-398 Page 12

Page 14
Image 14
Bard WA423, WA602, WA491, WA484, WA381 Wiring - Main Power, Wiring - Low Voltage Wiring, Range, Table Thermostat Wire Size