Bard WA602, WA491, WA484, WA381, WA423 installation instructions Table Pressure Table Cooling

Models: WA423 WA381 WA484 WA491 WA602

1 21
Download 21 pages 18.9 Kb
Page 20
Image 20
TABLE 10

TABLE 10

PRESSURE TABLE

COOLING

Air Temperature Entering Outdoor Coil °F

 

Return Air

 

 

 

 

 

 

 

 

 

 

Model

Temperature

Pressure

75

80

85

90

95

100

105

110

115

 

 

 

 

 

 

 

 

 

 

 

 

 

75 deg. DB

Low Side

74

74

75

76

78

79

79

80

81

 

62 deg. WB

High Side

175

187

202

216

232

249

265

284

302

WA381

80 deg. DB

Low Side

79

79

80

81

83

84

85

86

87

67 deg. WB

High Side

179

192

207

222

238

255

272

291

310

 

 

85 deg. DB

Low Side

82

82

83

84

86

87

88

89

90

 

72 deg. WB

High Side

185

199

214

230

246

264

252

301

321

 

75 deg. DB

Low Side

70

72

73

75

76

77

78

79

79

 

62 deg. WB

High Side

207

220

235

251

266

283

300

318

337

WA423

80 deg. DB

Low Side

75

77

78

80

81

82

83

84

85

67 deg. WB

High Side

212

226

241

257

273

290

308

326

346

 

 

85 deg. DB

Low Side

78

80

81

83

84

85

86

87

88

 

72 deg. WB

High Side

219

234

249

266

283

300

319

337

358

 

75 deg. DB

Low Side

73

74

76

78

79

80

82

83

84

 

62 deg. WB

High Side

204

217

232

248

265

284

304

325

348

WA484

80 deg. DB

Low Side

78

79

81

82

84

86

87

89

90

67 deg. WB

High Side

210

223

238

254

272

291

312

334

357

 

 

85 deg. DB

Low Side

84

85

87

88

90

92

93

95

97

 

72 deg. WB

High Side

217

231

247

264

282

302

323

345

369

 

75 deg. DB

Low Side

70

71

71

72

73

75

76

77

79

 

62 deg. WB

High Side

199

213

227

244

260

279

298

320

341

WA491

80 deg. DB

Low Side

75

76

76

77

78

80

81

82

84

67 deg. WB

High Side

204

218

233

250

267

286

306

328

350

 

 

85 deg. DB

Low Side

78

79

79

80

81

83

84

85

87

 

72 deg. WB

High Side

211

226

241

259

276

296

317

339

362

 

75 deg. DB

Low Side

71

72

74

75

76

77

78

78

79

 

62 deg. WB

High Side

233

247

262

278

295

313

331

351

371

WA602

80 deg. DB

Low Side

76

78

79

80

81

82

83

84

85

67 deg. WB

High Side

237

253

269

285

303

321

340

390

381

 

 

85 deg. DB

Low Side

84

85

85

86

87

88

89

90

91

 

72 deg. WB

High Side

245

261

278

296

314

333

353

373

394

Low side pressure ± 2 PSIG

High side pressure ± 5 PSIG

Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instructions.

NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check condenser fan wiring. See “Condenser Fan Operation” on Page 14.

Manual 2100-398 Page 18