TROUBLESHOOTING

TROUBLESHOOTING

FAN BLADE SETTING DIMENSIONS

Shown in Figure 10 is the correct fan blade setting dimension for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.

FIGURE 9

FAN BLADE SETTING

TABLE 5

FAN BLADE DIMENSION

 

Dimension

Model

A

 

 

WA381

 

WA423

 

WA484

1.75

WA491

 

WA602

 

REMOVAL OF FAN SHROUD

1.Disconnect all power to the unit.

2.Remove the screws holding both grilles, one on each side of unit, and remove grilles.

3.Remove screws holding fan shroud to condenser and bottom. Nine (9) screws.

4.Unwire condenser fan motor.

5.Slide complete motor, fan blade, and shroud assembly out the left side of the unit.

6.Service motor/fan as needed.

7.Reverse steps to reinstall.

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature (6” from compressor) as shown in Table 6.

TABLE 6

REFRIGERANT CHARGE

 

Rated

95 OD

82 OD

Model

Airflow

Temperature

Temperature

 

 

 

 

WA381

1100

50 - 48

48 - 46

 

 

 

 

WA423

1400

52 - 54

64 - 66

 

 

 

 

WA484

1550

54 - 56

65 - 67

 

 

 

 

WA491

1250

48 - 46

47 - 45

 

 

 

 

WA602

1700

53 - 55

60 - 62

 

 

 

 

The suction line temperatures in table above are based upon 80° F dry bulb / 67° F wet bulb (50% R.H.) temperature and rated airflow across the evaporator during cooling cycle.

TABLE 7

INDOOR BLOWER PERFORMANCE

CFM @ 230V

 

 

WA423, WA484

 

 

WA602

 

 

 

 

 

 

 

 

 

 

 

Low 230V

High 230V

Low 230V

High 230V

E.S.P.

 

 

 

 

 

 

 

 

Dry Coil

Wet

Dry Coil

Wet

Dry Coil

Wet

Dry Coil

Wet

In H20

Coil

Coil

Coil

Coil

 

 

 

 

.0

1650

1600

1885

1800

1600

1450

2200

2000

.1

1550

1500

1770

1665

1525

1375

2100

1900

.2

1450

1400

1635

1540

- - -

- - -

2000

1800

.3

1350

1300

1500

1400

- - -

- - -

1875

1700

.4

1300

1175

1370

1285

- - -

- - -

1775

1600

.5

- - -

- - -

1250

1150

- - -

- - -

1650

1475

Table 7A on Page 18 for models WA381 and WA491

Manual 2100-398 Page 16

Page 18
Image 18
Bard WA381 Troubleshooting, Fan Blade Setting Dimensions, Removal Of Fan Shroud, Refrigerant Charge, Fan Blade Dimension