FAN BLADE SETTING DIMENSIONS
Shown in Figure 17 are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.
Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.
FIGURE 17
FAN BLADE SETTING
TABLE 8
FAN BLADE DIMENSION
Model | Dimension A | |
|
| |
WH301 | 1.25" | |
WH361 | ||
| ||
|
|
The suction line temperatures in Table 9 are based upon 80ºF dry bulb/67ºF wet bulb (50 percent R.H.) temperature and rated airflow across the evaporator during cooling cycle.
TABLE 10
INDOOR BLOWER PERFORMANCE
CFM AT 230 VOLTS
|
| WH301, WH361 | |
|
|
| |
E.S.P. | Low Speed | High Speed | |
|
|
| |
|
|
| |
In H2O | Dry Coil / | Wet Coil | Dry Coil / Wet Coil |
.0 | 950 / | 935 | 1,395 / 1,315 |
|
|
|
|
.1 | 930 / | 915 | 1,340 / 1,270 |
|
|
|
|
.2 | 910 / | 885 | 1,285 / 1,190 |
|
|
|
|
.3 | 855 / | 830 | 1,205 / 1,100 |
|
|
|
|
.4 | 800 / | 755 | 1,110 / 1,000 |
|
|
| |
.5 | 1,005 / 870 | ||
|
|
| |
.6 | |||
|
|
|
|
REMOVAL OF FAN SHROUD
1.Disconnect all power to unit.
2.Remove the screws holding both grilles, one on each side of unit, and remove grilles.
3.Remove screws holding fan shroud to condenser and bottom – nine (9) screws.
4.Unwire condenser fan motor.
5.Slide complete motor, fan blade, and shroud assembly out the left side of the unit.
6.Service motor/fan as needed.
7.Reverse steps to reinstall.
REFRIGERANT CHARGE
The correct system
TABLE 9
SUCTION LINE TEMPERATURES
| Rated | 95 F OD | 82 F OD |
Model | Airflow | Temperature | Temperature |
|
|
|
|
WH301 | 1,100 | 56 - 58 | 63 - 65 |
|
|
|
|
WH361 | 1,100 | 49 - 51 | 66 - 68 |
|
|
|
|
TABLE 11
CFM AND ESP
| j | j |
|
| Rated | Rated | Recommended |
Model | CFM | ESP | Airflow Range |
|
|
|
|
WH301 | 1,000 | .30 | 930 - 1,300 |
WH361 | 1,100 | .30 | 930 - 1,350 |
|
|
|
|
Rated CFM and ESP on high speed tap
TABLE 12
MAXIMUM ESP OF OPERATION
ELECTRIC HEAT ONLY
|
| Front Outlet | Top Outlet | ||
|
|
|
|
|
|
|
| Low | High | Low | High |
Model | Speed | Speed | Speed | Speed | |
|
|
|
|
|
|
| A00 | .50 | .50 | .50 | .50 |
WH301 | A05 | .40 | .50 | .40 | .50 |
WH361 | A10 | .35 | .40 | .25 | .40 |
| A15 | .35 | .40 | NA | NA |
|
|
|
|
|
|
| B00 | .50 | .50 | .50 | .50 |
WH301 | B06 | .40 | .50 | NA | NA |
WH361 | B09 | .35 | .45 | .30 | .40 |
| B15 | .35 | .45 | NA | NA |
|
|
|
|
|
|
| C00 | .50 | .50 | .50 | .50 |
WH301 | C06 | .50 | .50 | NA | NA |
WH361 | C09 | .30 | .40 | .35 | .45 |
| C15 | .30 | .40 | NA | NA |
|
|
|
|
|
|
Values shown are for units equipped with standard 1" throwaway filter or 1" washable filter. Derate ESP by
.15 for 2" pleated filter.