Bard WH602, WH483, WH421 Fan Blade Setting Dimensions, Removal Of Fan Shroud, Refrigerant Charge

Models: WH421 WH483 WH602

1 23
Download 23 pages 40 Kb
Page 21
Image 21
FAN BLADE SETTING DIMENSIONS

FAN BLADE SETTING DIMENSIONS

Shown in the drawing in Figure 11 are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.

FIGURE 11

FAN BLADE SETTING

TABLE 6

FAN BLADE DIMENSIONS

Model

Dimension A

 

 

WH421

 

WH483

1.75

WH602

 

 

 

MIS-1190

REMOVAL OF FAN SHROUD

1.Disconnect all power to unit.

2.Remove the screws holding both grilles – one on each side of unit – and remove grilles.

3.Remove screws holding fan shroud to condenser and bottom – (9) screws.

4.Unwire condenser fan motor.

5.Slide complete motor, fan blade, and shroud assembly out the left side of the unit.

6.Service motor/fan as needed.

7.Reverse steps to reinstall.

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature (6 inches from compressor) as shown in the Table 7.

TABLE 7

SUCTION LINE TEMPERATURES

 

Rated

95°F O.D.

82°F O.D.

Model

Airflow

Temperature

Temperature

WH421

1400

52 -- 54

62 -- 64

WH483

1550

53 -- 55

62 -- 64

WH602

1700

52 -- 54

61 -- 63

 

 

 

 

The suction line temperatures in Table 7 are based upon 80ºF dry bulb/67 degrees F wet bulb (50 percent R.H.) temperature and rated airflow across the evaporator during cooling cycle.

TABLE 8

RECOMMENDED OPERATING RANGES

 

Rated

Rated

Recommended

Model

CFM *

ESP *

Air Flow Range

WH421

1400

.30

1600 -- 1150

 

 

 

 

WH483

1550

.20

1750 -- 1285

 

 

 

 

WH602

1700

.30

1950 -- 1375

 

 

 

 

*Rated CFM and ESP on high speed tap.

TABLE 9

INDOOR BLOWER PERFORMANCE

CFM @ 230V

 

 

WH421, WH483

 

 

WH602

 

 

 

 

 

 

 

 

 

 

E.S.P.

Low 230V

High 230V

Low 230V

High 230V

 

 

 

 

 

 

 

 

In H2O

Dry Coil

Wet Coil

Dry Coil

Wet Coil

Dry Coil

Wet Coil

Dry Coil

Wet Coil

.0

1650

1600

1885

1800

1600

1450

2200

2000

.1

1550

1500

1770

1665

1525

1375

2100

1900

.2

1450

1400

1635

1540

 

 

2000

1800

.3

1350

1300

1500

1400

 

 

1875

1700

.4

1300

1175

1370

1285

 

 

1775

1600

.5

-----

-----

1250

1150

 

 

1650

1475

Manual 2100-399 Page 19

Page 21
Image 21
Bard WH602, WH483 Fan Blade Setting Dimensions, Removal Of Fan Shroud, Refrigerant Charge, Figure Fan Blade Setting Table