Baxi Potterton 24/1.0 operating instructions List of Error Codes, 11.1

Models: 24/1.0

1 24
Download 24 pages 52.88 Kb
Page 18
Image 18

In the table below: - PCB = Main Control Board, BCU = Burner Control Unit.

 

 

11.0 Error Codes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UR = User Reset, AR = Automatic Reset, ARP = Automatic Reset after Power Down

 

 

 

 

 

 

 

 

 

11.1

 

List of Error Codes

 

 

 

 

 

 

 

 

 

 

NOTE: An automatic reset is only done if the fault condition has cleared.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Error code: Display

Description

 

 

 

 

Lockout/Reset action

 

 

 

 

 

 

 

 

Eng

Sup

 

10: Outside sensor

Fault outside temp sensor1

 

 

 

 

AR

 

AR

 

 

20: Boiler flow sensor

Fault boiler flow temp sensor

 

 

 

 

AR

 

AR

 

 

40: Boiler return sensor

Fault return temp sensor boiler

 

 

 

 

AR

 

AR

 

 

50: DHW tank sensor

Fault DHW1 sensor

 

 

 

 

AR

 

AR

 

 

60: Room sensor 1

Fault room temp sensor HC1

 

 

 

 

AR

 

AR

 

 

65: Room sensor 2

Fault room temp sensor HC2

 

 

 

 

AR

 

AR

 

 

83: BSB short-circuit

Boiler system bus short-circuit

 

 

 

 

AR

 

AR

 

 

84: BSB address collision

More then 1 room units are assigned to the same HC

 

 

 

 

 

 

 

 

 

 

Assign one of them to HC2 or assign QAA7x not as room unit

 

AR

 

AR

 

85: Radio communication

Communication to radio device interrupted

 

 

 

 

AR•

 

AR•

 

 

91: Data loss in EEPROM

Failure in Class B-SW: Irreparable data loss in EEPROM

 

 

 

 

NRP

 

NRP

 

 

92: Device electronics error

RAM failure, HBC processor register failure, blocking chain

 

 

 

 

 

 

 

 

 

undefined (toggling), safety chain discrepancy.

 

 

 

 

 

 

 

 

 

 

Reset: Press Service Reset within 20 seconds after Power up

 

NRP

 

NRP

 

95: Time of day invalid

The real time clock unit detected corrupted time of day.

 

 

 

 

 

 

 

 

 

96: Minor SW failure

Failure in Class B-SW: Stack overflow or program sequence failure

 

AR

 

AR

 

 

97: SW or HW failure

Failure in EGC-SW which causes non-volatile lock.

 

 

 

 

NRP

 

NRP

 

 

127: Legionella temperature

Legionella temperature not achieved within 48 hours

 

 

 

 

AR+

 

AR+

 

 

157: Boiler Flow Overheat stat

Boiler flow overheat thermostat / safety chain open

 

 

 

 

UR

 

UR

 

 

158: Condensate

Condensate switch of safety chain opened

 

 

 

 

UR

 

UR

 

 

164: Flow

Low flow or faulty flow switch

 

 

 

 

AR

 

AR

 

 

257: Pack sensor

Fault pack temp sensor

 

 

 

 

 

 

 

 

 

258: Pack over- temp

Internal ambient temperature to high

 

 

 

 

AR

 

AR

 

 

259: CJC sensor

Fault cold junction compensation sensor

 

 

 

 

AR

 

 

 

 

261: Loss of Engine flame

No flame after five ignition tries in Engine

 

 

 

 

UR

 

 

 

 

262: Loss of Supplementary flame

No flame after five ignition tries in Supplementary

 

 

 

 

 

 

UR

 

 

263: Engine BCU failure

Multiple communication request of Engine Burner Control Unit

 

 

 

 

 

 

 

unsuccessful.

 

 

 

 

 

 

 

 

 

 

1) Failure caused by BCU

 

 

 

 

ARP

 

 

 

 

 

2) BCU Communication Timeout on Main Control Board

 

 

 

 

AR

 

 

 

 

264: Supp. BCU failure

Multiple communication request of Supp. Burner Control Unit

 

 

 

 

 

 

 

unsuccessful.

 

 

 

 

 

 

 

 

 

 

1) Failure caused by BCU

 

 

 

 

 

 

ARP

 

 

2) BCU Communication Timeout on Main Control Board

 

 

 

 

 

 

AR

 

265: BCU failure

Not supported in Main Control Board

 

 

 

 

 

 

 

 

 

270: excessive temp. diff.

Excessive max temperature difference across the heat exchanger

 

 

 

 

 

 

 

during 5 minutes or excessive limit temperature difference.

 

 

 

 

 

 

 

 

 

If temperature difference fell below (threshold - switching

 

 

 

 

 

 

 

 

 

 

differential boiler): automatic reset

 

 

 

 

 

 

 

 

 

 

- when the maximum setting was exceeded immediately

 

 

 

 

AR

 

AR

 

 

- when the limit value was exceeded after 10 minutes

 

 

 

 

 

 

AR 10’

 

274: Dry fire protection

Flow switch did not close within 4 minutes

 

 

 

 

UR

 

UR

 

 

 

 

 

 

 

 

 

 

278: Max Temp Rise

Maximum flow temperature rise exceeded, automatic reset after

 

 

 

 

 

 

 

10 minutes

 

 

 

 

 

 

AR 10’

 

 

 

 

 

 

 

 

 

 

 

 

 

• After 10 minutes or after down power (ARP)

+ Will clear message if 65°C is achieved - does not inhibit appliance on.

18© Baxi Heating UK Ltd 2010

Page 18
Image 18
Baxi Potterton 24/1.0 operating instructions List of Error Codes, 11.1