18.0 Fault Finding

Refer to Section 16.0 “Illustrated Wiring Diagram” for position of terminals and components

Central Heating - Follow operational sequence

Turn selector switch to

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The display illuminates

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Error 110 flashing

 

 

 

 

 

YES

Error 130 flashing

 

 

 

 

 

Error 133 flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

Error 20, 28 or 50 flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

Error 119 flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn Central Heating

 

 

 

 

 

NO

thermostat to Maximum.

Pump runs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

Error 125 or 193 flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

3-way valve is open to Central

Heating circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

Fan runs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan runs at correct speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Spark at ignition electrodes for

NO

up to 5 seconds and for 3

 

 

 

attempts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Go to section ‘A’

 

Turn the selector switch to

YES

 

reset position for 5 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Go to section ‘E’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Go to section ‘C’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

Ensure all controls (and

 

YES

 

integral clock if fitted) are

 

 

calling for heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ensure that primary

 

 

 

 

 

circulation is OK & that

 

 

 

 

 

there is no blockage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Go to section ‘K’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Error 160 flashing

 

 

 

 

 

Go to section ‘D’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Error 160 flashing

 

 

 

 

 

Go to section ‘L’

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

Error 133 flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Go to section ‘F’

 

 

 

 

 

 

 

 

 

 

 

If the error 110 is still flashing.

Go to section ‘J’

Ensure controls are set to

demand and verify the

contacts are closed

Go to section ‘B’

Go to section ‘H’

Turn the selector switch to

reset

 

YES

Burner lights

 

 

 

YES

NO

Burner output modulates to maintain the temperature set

Burner does not stay alights

after 5 seconds

Check the Central Heating

NTC sensor

Go to section ‘E’

Error 130 flashing

Go to section ‘M’

YES

Error 133 flashing Go to section ‘I’

YES

Burner goes out

YES

Fan stops after 10 seconds

YES

Pump continues to run for 3

minutes

(room thermostat open)

YES

Operation sequence

successful

52© Baxi Heating UK Ltd 2012

Page 52
Image 52
Baxi Potterton Condensing Combination Boiler Error 133 flashing, Pump runs, Heating circuit, Reset position for 5 seconds

Condensing Combination Boiler specifications

The Baxi Potterton Condensing Combination Boiler is a sophisticated heating solution designed to meet the demands of modern households while promoting energy efficiency. This state-of-the-art boiler combines both heating and hot water capabilities into a compact unit, making it an ideal choice for homes with limited space.

One of the standout features of the Baxi Potterton Condensing Combination Boiler is its impressive energy efficiency. With a high energy efficiency rating, these boilers can significantly reduce energy bills and minimize carbon footprints. The condensing technology maximizes heat recovery, allowing the boiler to utilize heat that would otherwise be lost in traditional systems. By extracting more energy from the combustion process, homeowners can enjoy reliable heating and hot water without the typical energy waste associated with older boilers.

The Baxi Potterton range is engineered for easy installation and maintenance, featuring a lightweight design that simplifies the fitting process. The built-in digital control system allows homeowners to easily adjust settings for optimal comfort and energy usage. Additionally, the boiler includes a frost protection feature, making it a reliable option for homes in colder climates.

Another key characteristic of the Baxi Potterton Condensing Combination Boiler is its powerful hot water delivery system. The combination boiler provides instant hot water on demand, eliminating the need for a separate water tank. This ensures that households have a constant supply of hot water for showers, cooking, and other domestic needs, without long wait times.

Safety is a top priority with the Baxi Potterton. The boiler is equipped with multiple safety features, including pressure relief valves and safety cut-off systems, ensuring peace of mind for homeowners. The compact design further includes a quiet operation feature, which is particularly beneficial for households where noise levels need to be kept to a minimum.

In summary, the Baxi Potterton Condensing Combination Boiler is a highly efficient, compact, and user-friendly solution for home heating and hot water needs. With its advanced technology and strong emphasis on safety, it stands out as a reliable choice for modern households looking to improve energy efficiency while maintaining comfort. Whether you are replacing an old boiler or installing a new system, the Baxi Potterton offers a perfect blend of practicality and innovation.