18.0 Fault Finding
© Baxi Heating UK Ltd 2012

Fault Finding Solutions Sections

Is there 230V at:
Is there 230V at:
Main terminals L and N Check electrical supply
1. NO
Main terminal fuse Replace fuse Replace PCB
Display
illuminated
2. NO
PCB - X1 connector
terminals 1,2
Check wiring
3. NO
NO
A
Pump Replace pump
1. YES
PCB - X3 connector terminals 3 & 4 Replace PCB
2. NO
Change pump supply cable
YES
B
CH system pressure less than 0.5 bar Re-pressurise system
1. YES
Check the tap of the automatic air
vent is opened Open the automatic air vent
2. NO
C
1.
NO
YES
Fan connections correct at fan. PCB -
X2 connector, is 230V AC across
terminals 5 & 7 Fan jammed or faulty winding
Replace PCB
Replace fan
YES
D
If pump jammed, release NO
NO
Replace water
pressure switch
Check connection water pressure
switch terminal
COM - NO and PCB connector
X400 terminals 3,4
YES