Beckett CF1400, CF2300 manual Start the burner, Hot Gas Puff-back and Heavy Smoke Hazard

Models: CF2300 CF1400

1 24
Download 24 pages 57.78 Kb
Page 19
Image 19
‰Set appliance limit controls

‰Set appliance limit controls

ySet the appliance limit controls in accordance with the appliance manufacturer’s recommendations.

yMove the low-fire hold switch (not shown) to the low fire hold position. This will hold the burner in low fire during initial start-up.

‰Prepare the fuel unit for air venting

Hot Gas Puff-back and

Heavy Smoke Hazard

Failure to bleed the pump properly could result in unstable combustion, hot gas puff-back and heavy smoke.

yDo not allow oil to intermittently spray into a hot combustion chamber while bleeding.

yInstall a gauge in the nozzle discharge port tubing or fully open the pump bleed valve to prevent oil spray from accumulating in the combustion chamber when venting air from the fuel pump.

yEnsure that all bubbles and froth are purged from the oil supply system before tightening the pump air bleed valve.

yTo vent air from one-pipe oil systems, attach a clear hose to the vent plug on the fuel unit. Provide a container to catch the oil. Loosen the vent plug.

yVent the air as described under ‘Start the Burner’.

Start the burner

Professional Service

Required

Incorrect installation, adjustment, and use of this burner could result in severe personal injury, death, or substantial property damage from fire, carbon monoxide poisoning, soot or explosion.

Please read and understand the manual supplied with this equipment. This equipment must be installed, adjusted and put into operation only by a qualified individual or service agency that is:

yLicensed or certified to install and provide technical service to oil heating systems.

yExperienced with all applicable codes, standards and ordinances.

yResponsible for the correct installation and commission of this equipment.

ySkilled in the adjustment of oil burners using combustion test instruments.

The installation must strictly comply with all applicable codes, authorities having jurisdiction and the latest revision of the National Fire Protection Association Standard for the installation of Oil-burning Equipment, NFPA 31 (or CSA B139 and B140 in Canada).

Regulation by these authorities take precedence over the general instructions provided in this installation manual.

Do not proceed unless all prior steps in this manual have been completed.

Explosion and Fire

Hazard

Failure to follow these instructions could lead to equipment malfunction and result in heavy smoke emission, soot-up, hot gas puff-back, fire and asphyxiation hazards.

y Do not attempt to start the burner when excess oil has accumulated in the appliance, the appliance is full of vapor, or when the combustion chamber is very hot.

y Do not attempt to re-establish flame with the burner running if the flame becomes extinguished during start-up, venting, or adjustment.

y Vapor-Filled Appliance: Allow the unit to cool off and all vapors to dissipate before attempting another start.

y Oil-Flooded Appliance: Shut off the electrical power and the oil supply to the burner and then clear all accumulated oil before continuing.

y If the condition still appears unsafe, contact the Fire Department. Carefully follow their directions.

y Keep a fire extinguisher nearby and ready for use.

Form 6104 BCF23-R05