Pre-installation checklist

Instruction Manual – Model CF1400 Oil Burner

Pre-installation checklist

Combustion air supply

The burner requires combustion air and ventilation air for reliable operation. Assure that the building and/or com- bustion air openings comply with National Fire Protection Standard for Oil-Burning Equipment, NFPA 31. For appli- ance/burner units in confined spaces, the room must have an air opening near the top of the room plus one near the floor, each with a free area at least one square inch per 1,000 Btu/hr input of all fuel burning equipment in the room. For other conditions, refer to NFPA 31 (CSA B1139- M91 in Canada).

If there is a risk of the space being under negative pressure or of exhaust fans or other devices depleting available air for combustion and ventilation, the appliance/burner should be installed in an isolated room provided with out- side combustion air.

Clearances

With the burner installed in the appliance, there must be adequate space in front of and on the sides of the burner to allow access and operation. Verify that the clearance di- mensions comply with all local codes and with the appli- ance manufacturer's recommendations.

Fuel supply

The fuel supply piping and tank must provide #1 or #2 fuel oil at pressure or vacuum conditions suitable for the fuel unit (oil pump) on the burner. Refer to fuel unit litera- ture in the literature envelope in the burner carton to verify allowable suction pressure.

The fuel unit is shipped without the by-pass plug installed for CF1400 ON/OFF burners. You must install this plug on two-pipe systems. DO NOT install the by-pass plug in the fuel unit if connected to a one-pipe oil system. Failure to comply could cause fuel unit seal failure, oil leakage and potential fire and injury hazard.

If fuel supply is level with or higher than fuel unit —

When the fuel unit is not required to lift the oil, the instal- lation is usually suitable for either a one-pipe or two-pipe oil system. The oil pressure at the inlet of the fuel unit must not exceed 3 psig.

See Figure 8 for one-pipe fuel supply installations. See Figure 9 for two-pipe fuel supply installations.

If fuel supply is below the fuel unit —

Use a two-pipe oil system when the fuel unit must lift the oil more than 8 feet if burner is equipped with a B fuel unit

— or more than 2 feet if burner is equipped with an H fuel unit. The return line provided by the two-pipe system is needed to purge the air from the fuel lines and minimize the likelihood of air-related problems during operation.

Vent system

The flue gas venting system must be in good condition and must comply with all applicable codes.

Electrical supply

Verify that the power connections available are correct for the burner. All power must be supplied through fused dis- connect switches.

Verify burner components —

Burner box, Model CF1400

Air tube assembly (selected per following)

Mounting flange kit

Pedestal mounting assembly kit (recommended)

Oil nozzle, per Table 1 — Use only 45° to 70° solid pat- tern nozzles unless otherwise shown by appliance manu- facturer.

Find the required firing rate in the 300 psig column (fac- tory-set fuel unit pressure).

Select the corresponding nozzle from column 1 (Rated gph @ 100 psig).

Table 1 - Nozzle capacitites

Rated
Pressure - pounds per square inch
gph @

 

 

 

 

 

 

125

150

175

250

275

300

100 psig

 

 

 

 

 

 

 

2.00

2.24

2.45

2.65

3.16

3.32

3.46

 

 

 

 

 

 

 

2.25

2.52

2.76

2.98

3.56

3.73

3.90

 

 

 

 

 

 

 

2.50

2.80

3.06

3.31

3.95

4.15

4.33

 

 

 

 

 

 

 

2.75

3.07

3.37

3.64

4.35

4.56

4.76

 

 

 

 

 

 

 

3.00

3.35

3.67

3.97

4.74

4.97

5.20

 

 

 

 

 

 

 

3.50

3.91

4.29

4.63

5.53

5.80

6.06

 

 

 

 

 

 

 

4.00

4.47

4.90

5.29

6.32

6.63

6.93

 

 

 

 

 

 

 

4.50

5.04

5.51

5.95

7.11

7.46

7.79

 

 

 

 

 

 

 

5.00

5.59

6.12

6.61

7.91

8.29

8.66

 

 

 

 

 

 

 

5.50

6.15

6.74

7.28

8.70

9.12

9.53

 

 

 

 

 

 

 

6.00

6.71

7.35

7.94

9.49

9.95

10.39

 

 

 

 

 

 

 

6.50

7.27

7.96

8.60

10.28

10.78

11.26

 

 

 

 

 

 

 

7.00

7.83

8.57

9.26

11.07

11.61

12.12

 

 

 

 

 

 

 

7.50

8.39

9.19

9.92

11.86

12.44

12.99

 

 

 

 

 

 

 

8.00

8.94

9.80

10.58

12.65

13.27

13.86

 

 

 

 

 

 

 

4

Form 6104 BCF14N-R0299

Page 4
Image 4
Beckett CF 1400 Pre-installation checklist, Combustion air supply, Clearances, Fuel supply, Vent system, Electrical supply