Instruction Manual – Model CF1400 Oil Burner
Figure 12 – Air damper assembly
|
|
| h |
|
|
|
|
| 6 | 7 | 8 | 9 | 10 | 11 |
|
5 |
|
|
| 12 | |||
|
|
|
|
|
| ||
4 |
|
|
|
|
|
|
|
3 |
|
|
|
|
|
|
|
2 |
|
|
|
|
|
|
|
1 |
|
|
|
|
|
|
|
0 |
|
|
|
|
|
|
|
k
m
Legend (Figure 12)
hDamper label - position indicator for air adjusting plate
Table 5 – Initial air adjusting plate settings (damper position)
Approximate | Firing rate, gph | ||
|
|
| |
head settings | Tube “A” |
| Tube “B” |
|
| ||
|
|
|
|
0 | 4.00 |
| 4.00 |
|
|
|
|
1 | 4.50 |
| 7.50 |
|
|
|
|
2 | 5.00 |
| 8.00 |
|
|
|
|
3 | 6.00 |
| 9.00 |
|
|
|
|
4 | 7.00 |
| 10.00 |
|
|
|
|
5 | 7.50 |
| — |
|
|
|
|
6 | 8.00 |
| — |
|
|
|
|
7 – 10 | — |
| — |
|
|
| |
| These settings are approximate, and can | ||
NOTE | vary depending on actual job conditions | ||
| and overfire pressure. |
| |
|
|
|
|
❏Set appliance limit controls
•Set the appliance limit controls in accordance with the appliance manufacturer's recommendations.
❏Prepare the fuel unit for air venting
| • | To vent air from |
k Damper indicator - permanently attached to damper |
| the vent plug on the fuel unit. Provide a container to catch |
|
| the oil. Loosen the vent plug. |
m Air adjusting plate - sets air position | • | Vent the air as described under Start the burner, page 14. |
Form 6104 | 13 |