Beckett CF 1400 Set appliance limit controls, Prepare the fuel unit for air venting

Models: CF 1400

1 16
Download 16 pages 7.8 Kb
Page 13
Image 13
Figure 12 – Air damper assembly

Instruction Manual – Model CF1400 Oil Burner

Figure 12 – Air damper assembly

 

 

 

h

 

 

 

 

 

6

7

8

9

10

11

 

5

 

 

 

12

 

 

 

 

 

 

4

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

k

m

1409o-2

Legend (Figure 12)

hDamper label - position indicator for air adjusting plate

Table 5 – Initial air adjusting plate settings (damper position)

Approximate

Firing rate, gph

 

 

 

head settings

Tube “A”

 

Tube “B”

 

 

 

 

 

 

0

4.00

 

4.00

 

 

 

 

1

4.50

 

7.50

 

 

 

 

2

5.00

 

8.00

 

 

 

 

3

6.00

 

9.00

 

 

 

 

4

7.00

 

10.00

 

 

 

 

5

7.50

 

 

 

 

 

6

8.00

 

 

 

 

 

7 – 10

 

 

 

 

 

These settings are approximate, and can

NOTE

vary depending on actual job conditions

 

and overfire pressure.

 

 

 

 

 

Set appliance limit controls

Set the appliance limit controls in accordance with the appliance manufacturer's recommendations.

Prepare the fuel unit for air venting

 

To vent air from one-pipe oil systems, attach a clear hose to

k Damper indicator - permanently attached to damper

 

the vent plug on the fuel unit. Provide a container to catch

 

 

the oil. Loosen the vent plug.

m Air adjusting plate - sets air position

Vent the air as described under Start the burner, page 14.

Form 6104 BCF14N-R0299