CLEANING & MAINTENANCE

INFRARED/RADIANT COMPACT BROILER

VENTILATION

WARNING

Improper ventilation can result in personal injury or death. Ventilation, which fails to properly remove flue products, can cause headaches, drowsiness, nausea, or could result in death.

The flue vent, located at the top of the unit, must not be blocked or covered at any time.

All gas appliances must be installed in such a manner that the flow of combustion and ventilation air is not obstructed. Provisions for adequate air supply must be provided.

NOTICE

Proper ventilation is the owner’s responsibility. Any problem due to improper ventilation will not be covered by the warranty.

Do not obstruct the front of the broiler since combustion air enters through this area. Be sure to inspect and clean the ventilation system according to the ventilation equipment manufacturer’s instructions.

If a ventilation canopy is used, it is recommended that the canopy extend 6" past the broiler and that the bottom edge be located 6'6" from the floor. Filters should be installed at an angle of 45° or more from the horizontal. This position prevents dripping grease and facilitates collecting the run-off grease in a drip pan under the filter.

A strong exhaust fan tends to create a vacuum in the room and may interfere with burner performance or may extinguish pilot flames. Fresh air openings approximately equal to the fan area will relieve such a vacuum. The exhaust fan should be installed at least 2" above the vent opening on the top of the broiler.

If the broiler is connected directly to an outside flue, a CSA design-certified down draft diverter must be installed.

In case of unsatisfactory performance by any gas appliance, check the appliance with the exhaust fan turned OFF. Do this only long enough to check whether doing so corrects any problems with equipment performance. Then turn the exhaust fan back on and let it run to remove any exhaust that may have accumulated during the test.

GAS SUPPLY

The broiler is design-certified for operation on natural or propane gases. The broiler is shipped configured and adjusted for the type of gas specified by the purchaser, which is indicated on the serial plate (see Figure 1 on page 3). Connect the broiler ONLY to the type of gas for which it is configured and adjusted.

Infrared:

Gas Type

Total BTU/hour

Burner Orifice

Pilot Orifice

Min. Supply Pressure

Manifold Pressure

Natural Gas

40,000

No. 54 (P/N 1008754)

0.055 (P/N 1008754)

7" W.C.

4" W.C.

Propane

40,000

No. 64 (P/N 1008764)

0.036 (P/N 1008764)

11" W.C.

10" W.C.

Radiant:

Gas Type

Total BTU/hour

Burner Orifice

Pilot Orifice

Min. Supply Pressure

Manifold Pressure

Natural Gas

40,000

No. 52 (P/N 1008952)

0.055 (P/N 1008754)

7" W.C.

4" W.C.

Propane

40,000

No. 64 (P/N 1008764)

0.036 (P/N 1008764)

11" W.C.

10" W.C.

A model that mounts on the flue riser of a range will have a 3/8" rear gas connection (with a 3/8" male NPT connector) extending through the rear of the flue riser (see Figure 2 on page 5).

Wall-mount and countertop models will have a 3/8” rear gas connection (with a 3/8” male NPT connector). The gas connection can extend directly out the rear of the broiler (near the bottom right-rear corner).

Minimum supply pressure is 7" W.C. for natural gas, 11" W.C. for propane. An internal pressure regulator and shutoff valve are provided. If using a flexible-hose gas connection, the I.D. of the hose must not be smaller than the connector on the broiler, and must comply with ANSI Z21.69. Provide an adequate means of restraint to prevent undue strain on the gas connection. Test pressure should not exceed 14" W.C.

PAGE 6 OF 24

INSTALLATION & OPERATIONS MANUAL 1186529 REV 3 (12/06)

Page 6
Image 6
Blodgett B36-RAD, B48-RAD, B48-NFR, B36-NFR manual Ventilation, GAS Supply