4.8 | External alarm I/O connection |
Alarm inputs and outputs are supplied screw down terminal blocks. The screw terminal blocks are supplied with the unit.
Connecting the inputs
Each (alarm) input line can be switched by a contact from an external device between an numbered input and ground (G). Wire them as either Normally Open (N/O) or Normally Closed (N/C). Configure the alarm inputs as N/O or N/C in the menu system. The default is N/ O.
Specifications
Alarm input impedence: Internal
Input voltage range:
Input voltage threshold: low voltage 0.5 V maximum, high voltage 2 V minimum
Cable cross section: AWG
Connecting the alarm outputs
The four alarm output relays respond to input alarms and triggers. Configure the alarm outputs as N/O or N/C in the menu system. Only connect resistive loads to the alarm output relays. Do not exceed 30 Vac, 40 Vdc, 500 mA (continuous), or 10 VA on an alarm output relay's contacts.
DANGER!
Electrical voltage.
Risk of electric shock and damage to the unit.
The contacts must not be used at AC line voltages.
Specifications
Switching current (resistive): 500 mA maximum
Switching voltage (resistive): 30 VAC/40 VDC maximum
Cable cross section: AWG
Figure | 4.9 | Alarm input connector for |
Figure | 4.10 | Alarm input connector for |
Figure 4.11 Alarm output connector