DS9400 Series  Release Notes for Firmware V2.07  Trademarks

DS9400 Series Release Notes for Firmware V2.07 Trademarks

Upgrade Information

Trademarks

Gentex™ is a trademark of Gentex Corporation, Fire Protection Group

CleanMe® is a registered trademark of GE Interlogix

1.0 Fixed Items in Firmware Version V2.07

The D9400 Series Fire Alarm Control Panel (FACP)

V2.07 fixes two bugs:

If this firmware is installed in a control panel that has been running version 1.x software, it is necessary to erase the old programming in the control panel and re- select the control panel type when the control panel is first powered up. Be careful to select “1-DS9400”- an incorrect selection cannot be undone.

3.0 Fixed Items in Firmware Version 2.05

When the Drill button was pressed, only the Local Notification Appliance Circuits would activate. This has been corrected, and the DS9484 Remote NAC supply also activates.

In Firmware Version V2.06, a bug was created when silencing a multiple output module (DS9488/B or DS9489/B), causing some outputs not to silence. This worked correctly in other firmware versions, but worked incorrectly when changing the silence priority feature.

2.0 Fixed Items in Firmware Version 2.06

Version 2.06 firmware for the DS9400 Series Fire alarm Control Panels (FACP) incorporates a change to Preassigned Zone 61 and a bug fix for Outputs assigned to Silencable points.

Preassigned Zone 61 – General Water flow (Silencable) has been changed to a Non- Silencable Zone type.

Preassigned Zone 53 – General Fire alarm (Silencable) has been fixed so that a Non- Silencable point will take priority over a Silencable point.

1.This condition may happen when both Silencable and Non-Silencable points are mapped to the same output.

2.Version 2.05 and prior would configure the output to Silencable or Non-Silencable depending on the last event type activated.

Version 2.05 firmware for the DS9400 Series Fire Alarm Control Panels (FACP) incorporates a bug fix for auto-programming and updates the panel to work with the DS9431 with V1.04 ROM or later.

Auto-programming.

1.When selecting a device type of I/O, the first address programs correctly but if any device option is selected other than “no device,” the second address results in an “Address Error 2.” This V2.05 ROM fixes this issue.

2.The Auto-program feature of the DS9400 with V2.04 ROM does not work properly if a DS9431 V1.04 MUX driver or later is installed. The DS9400 with V2.05 ROM is backwards compatible with V1.04 and earlier versions of the DS9431.

4.0 Fixed Items in Firmware Version 2.04

Version 2.04 firmware for the DS9400 Series Fire Alarm Control Panels (FACP) incorporates several new features and improvements:

Gentex™ Sync Protocol. The control panel can now send Gentex protocol to Gentex Notification Appliance Circuit (NAC) devices. Gentex NAC devices can be added directly to the NAC circuits without a sync module.

CleanMe®. The control panel recognizes the Clean-Me signal from Detection System’s F220 Series Smoke Detectors. If the smoke detectors get dirty, a signal is sent on the two-wire loop, and the control panel will annunciates that there is a dirty detector on the loop.