Fixed Items Since Firmware Version 1.08

DS9400 Series Release Notes for Firmware V2.07 7.0

Fixed Items Since Firmware Version 1.08

 

 

DS9431 Accidental Removal (DS9400M only): On control panels running firmware version 2.02 or earlier, if the wires on the keypad option bus are momentarily shorted for less than a second, the DS9431 Multiplex Expansion Module may stop working. If this occurs, the display will show “MUX NOT DETECTED” and the Trouble buzzer will sound. If the */Clear key is pressed, the DS9431 will be uninstalled.

Firmware version 2.03 corrects this problem. If the DS9431 should fail, a new message, “CALL FOR SERVICE,” will be displayed along with the following message, “MUX NOT WORKING.” Pressing the */Clear key will silence the Trouble buzzer, but will neither clear the trouble messages nor uninstall the DS9431. If “MUX NOT WORKING, CALL FOR SERVICE” or INST.FLT MX EXP” is displayed, the control panel should be powered down by removing AC and standby battery connections, and then restarted. Doing so will restore the DS9431 to proper operation. If the problem is not corrected, please contact Technical Support at (888) 886-6189.

Make sure that you are at the control panel site with an available phone line before calling Technical Support.

To remove the DS9431 after installing firmware version 2.03, please contact Technical Support at (888) 886-6189.

DS9434 Four Point Expander Removal: To prevent the accidental removal of the DS9434, a new message “CALL FOR SERVICE,” is displayed. If you wish to remove a previously installed DS9434, please contact Technical Support at (888) 886-6189.

7.0Fixed Items Since

Boards shipped before August 31, 1999 must be modified according to Technical Service Note (P/N: 42363) to ensure that the battery test runs properly. Affected boards carry a lot number of 99 or lower and a date code of 9935 or earlier. Boards shipped after August 31, 1999 with a date code higher than 9935 are unaffected. See Figure 1 on page 3 for the location of the lot number and date code.

Figure 1: Firmware Version Label and Date Code Locations

1

3

2

XXXX

 

1 Lot Number Label

2 Firmware Version Label

3 Date Code Stamp

Do not exceed standby current ratings for the control panel. If the total current drawn

from the smoke power and option bus power terminals exceeds 1 amp, the system may not be able to switch to battery power when AC fails. Current drawn from NACs and auxiliary power does not impact battery transfer operation.

Firmware Version 1.08

AC Failure during Automatic Battery Test: The DS9400 FACP automatically tests the standby batteries every 180 seconds for two seconds. The system will now continue normal operation if an AC power failure occurs exactly during this two-second battery test window.

4

Bosch Security Systems 8/06 36925V