Bosch Appliances 5.0 DS9400 Series Version 2.03A October, Fixed Items in Firmware Version

Models: DS9400

1 8
Download 8 pages 35.95 Kb
Page 3
Image 3
DS9400 Series  Release Notes for Firmware V2.07  5.0

DS9400 Series Release Notes for Firmware V2.07 5.0

DS9400 Series Version 2.03A October, 2002

 

 

Wheelock Sync Protocol. This feature no longer requires the Detection Systems D411/D412 in order to produce Temporal Code 3.

Auto Silence Operation. The auto-silence operation is now correctly processed on a system configured to use the autosilence feature that powers up with a trouble condition.

Reorganized Phone Programming Menu. To better differentiate phone line features versus phone number features, the phone programming menu has been reorganized.

Relay Outputs. When an output is set to follow a point, the output releases when the silence key is pressed. This feature has been fixed and will now stay latched for elevator recall and fan control.

5.0 DS9400 Series Version

2.03A October, 2002

Version 2.03A firmware for the DS9400 Series Fire Alarm Control Panels incorporates a change in the Contact ID reports and a change in the Trouble Relay Function as described below.

Contact ID Reporting. The system can be programmed to send a periodic test report, E602, in Contact ID format. If any system troubles are present at the periodic test time, a new event, E608, which states “New event, off normal at time of periodic test report” is sent. Software versions 2.03 and before sent a generic system trouble P300 report.

General Trouble Relay Function for the onboard relays only. In order to provide an output that is energized when the control panel is operating normally, the operation of the “General Trouble" output type (Zone 62) has been changed.

The change is observed when Zone "A" for one of the two on-board relays is programmed using Zone 62 (General Trouble). For this output, the relay will be energized when there are no troubles present in the system. When there is a trouble, the relay will de-energize.

For this relay to function properly, Zones "B", "C", and "D" must be programmed with a value of "00". The General Trouble output function can not be combined with any other output function.

When communicating to the control panel using RPS, the control panel will report v2.03 software installed even when the upgrade v2.03A has been installed.

6.0 Fixed Items in Firmware Version 2.03

The following list of fixed items only applies to control panels that have version 2.03 firmware installed and a date code later than 9935. These items may still apply to control panels running an earlier version of firmware, and/or have a date code of 9935 or earlier.

“REPROGRAM SYS” Message: With firmware version 2.03, the System Trouble message, “TROUBLE EEPROM” has been changed to “REPROGRAM SYS.” This message will appear:

when the control panel is powered up for the first time with firmware version 2.03 installed

if there is an invalid EEPROM checksum

if the control panel has been defaulted improperly and system programming has not been performed

To clear the “REPROGRAM SYS” message, use the following procedure:

From the Main Menu, press the 0/Prog key to enter the Programming Menu. The Programming Menu will appear.

Reprogram the system according to site-specific information.

Exit the programming mode by pressing the */Clear key until the Main Menu reappears. If the control panel is defaulted from the programming mode, the “REPROGRAM SYS” message will not appear. When this message appears, check all programming entries from the built-in user interface, or from a remote connection using Bosch Security Systems’ RPS Remote Programming Software.