14 en ConnectionNetworking Cards

Terminal

 

Specifications Class A Style 7

 

 

 

FPE-1000-NW

Wired OUT+/-

Terminals used for outgoing loop

 

 

 

 

Wired IN+/-

Terminals used for return loop

 

 

 

Table 5.2 Specifications SLC Terminals Class A Style 7

Additional notes regarding Class A Style 7:

1.No T-taps allowed on Class A Style 7 network wiring.

2.The return side of the loop must be routed separately from the outgoing loop.

3.The return side must not share the same conduit or cable as the outgoing side of the loop.

4.Refer to NFPA 72 for additional requirements of Class A circuits.

Figure 5.1 Network Connections Example

Legend

1

2

3

4

5

Wire to Wire connection

Wire to Ethernet connection

Ethernet to Fiber Optic connection

Fiber Optic to Fiber Optic connection

Class A connection (Ethernet to Ethernet in this example)

NOTICE!

The network does not require an EOL resistor.

F.01U.214.374 01 2012.08

Installation Manual

Bosch Security System, Inc.

Page 14
Image 14
Bosch Appliances FPE-1000-NW, FPE-1000-NE, FPE-1000-NF Terminal Specifications Class a Style, Network Connections Example