D9000,G & GV2 Series Owner's Manual Supplement
7. | Press the [ENT] key to view the point’s hardware state: | |
|
| |
1PT### NORMAL HW if it is normal | 1PT### OPEN HW if it is opened | |
|
| |
1PT### SHORT HW if it is shorted | 1PT### MISSNG HW if it is missing | |
|
|
|
8. | Activate the point’s sensor and observe the appropriate state | |
| change. |
|
9. | Press the [NEXT] key to advance to the next invisible point | |
| within the scope of the keypad. | |
10. | Repeat steps 7 through 9 until all points are tested. |
On a D1260 keypad with the Passcode Controlled Menu enabled:
1.Press the [Menu>] soft key in the lower right corner.
2.Press the [Next>] soft key until the Invisible Walk Test? appears.
3.Press the corresponding soft key to activate the Invisible Walk Test function. The keypad shows the number of invisible points within the scope of the keypad: ### points remain to be tested.
5.Press the [View untested pts>] soft key to see 6 pts untested.
6.Press the [Next Pt>] soft key to view the first or next untested point:
[Point Text] |
|
|
Area #, Pt # |
|
|
[Point State] HW | Next | PT> |
<Exit | Prev | PT> |
|
|
|
7.Where [Point State] can be NORMAL,OPEN,SHORT, or MISSNG.
8.Activate the point’s sensor and observe the appropriate state change.
9.Repeat Steps 5 through 8 until all points are tested.
Bosch Security Systems 5/05 33267F | 9 |