| SERVICE PROCEDURE | ||||
|
|
|
|
|
|
| Pressure Switch Testing | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| DANGER |
|
|
| CAUTION |
|
| ||
|
|
|
| Be Careful When Making Voltage |
| |||||
| 120 volt exposure. To avoid personal injury, |
|
| Measurements or Jumping Terminals |
| |||||
| use caution while performing this procedure. |
|
| Not to Damage or Deform Connectors or |
| |||||
|
|
|
|
|
| Connector Pins. |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| PDV(S & T) Models |
|
| Vent Safety Switch |
|
Red reset button
Check pressure switch tubing to the pressure switch. Make sure tubing does not have kinks, holes, condensate, or dirt blocking air pressure to the switch. The tubing to the blower tap attaches to the - (minus) tap on the pressure switch.
Vent safety thermal switch on
Induced Draft Models (D80T725 & D65T625):
Induced Draft Models use a single tap pressure switch to measure vacuum in the flue collector. The pressure switch is located inside the control box (see photo to left). Connect a digital manometer to a tee in the pressure switch tubing and measure the vacuum with the blower operating. The vacuum should be in the range of
28