(See Figure 8).

Internet Version for Reference Only

Installation (Vent-Air Intake System Installation) continued-

1. Measure the vertical height “Y” required in your installation. (See Figure 7). Reference the appropriate Table A to determine number of vent-air intake kits required in your installation.

2. Measure the horizontal length “X” required in your installation (See Figure 7). Reference Table A to determine number of vent-air intake kits required in your installation.

3. Cut a 6-1/2 inch (16.5 cm) diameter minimum clearance hole in the wall at the point where the vent-air intake tubes will pass through the outside wall and connect with the direct vent-air intake terminal

(See Figure 8).

4. From outside the building, position the outer wall mount plate and direct vent-air intake terminal over the center of the opening. Mark the mounting screw hole locations. With a 3/16 inch (4.7 mm) diameter drill bit (not supplied), drill holes for the wall anchors (supplied). Install the wall anchors but DO NOT affix the outer wall mount plate and direct vent-air intake terminal to the wall at this time (See Figure 8). Note: Certain construction of walls may require the use of a different type of wall anchoring means than supplied. DO NOT modify the direct vent-air intake terminal or outer wall mount plate.

Figure 8.