10
Sacrificial anode rods have been installed in the tank head of the water heater to extend tank life. The removal of these
anodes for any reason will nullify the warranty. In areas where water is unusually active, an odor may occur at the hot
water faucet due to a reaction between the sacrificial anode and the impurities in the water. If this should happen,
alternative anodes may be purchased from the supplier that installed this water heater. This will minimize the odor while
protecting the tank. Additionally, the water heater should be flushed with appropriate dissolvers to eliminate any
bacteria.
This water heater MUST be installed indoors out of the wind and weather.
This water heater MUST NOT be installed in any location where gasoline or flammable vapors are likely to be
present, unless the installation is such to eliminate the probable ignition of gasoline or flammable vapors.
Water heaters in residential garages must be installed so that all burner(s) and ignition device(s) are located
not less than 18 inches (45.7 cm) above the floor and be located, or protected, to avoid physical damage. For
other installations, refer to local codes. In the absence of local codes, the water heater must be installed in
compliance with the National Fuel Gas Code, (ANSI Z223.1-Latest Edition) or CAN/CGA B149.1 Natural Gas
Installation Code (Latest Edition) or CAN/CGA B149.2 Propane Installation Code (Latest Edition).
UNPACKING
INSPECT SHIPMENT carefully for any signs of damage.
1. All equipment is carefully manufactured, inspected and packed.
2. Any claims for damage or shortage in shipment must be filed immediately with Bradford White Corporation and
noted on the Bill of Lading.
3. Remove all venting components and mixing valve from the combustion assembly compartment by removing
the latches.
NOTICE
The mixing valve, vent terminals and the condensate elbow that are supplied with this water
heater are stored at the top in the Combustion Assembly Compartment. To access these
parts, unlatch the top lid. Be sure to replace the top and relatch.
LOCATE WATER HEATER in front of final position before removing crate.
1. LOCATE so that venting connections will be short and direct.
2. THIS WATER HEATER IS SUITABLE FOR INSTALLATION ON A COMBUSTIBLE FLOOR. Do not install
this water heater directly on carpeting. If the water heater is to be installed on carpeting, it must be installed
on top of a metal or wood panel extending beyond the full width and depth of the appliance by at least three 3
inches (7.6 cm) in any direction or, if the appliance is to be installed in an alcove or closet, the entire floor
must be covered by the panel.
3. FOR BASEMENT INSTALLATION, provide a solid level elevated base such as concrete or other suitable pad
to raise the water heater at least 3 inches (7.6 cm) to provide a slope of inch (.3 cm) to ¼ inch (.6 cm) per
foot (.3 m) for the condensate line to a suitable drain.
4. Minimum clearance to combustible material is 0 inches for the Top, Sides, and Rear of this water heater.
However, it is recommended that at least 18 inches (45.7 cm) from the Top, 24 inches (61 cm) from the
Front, 4 inches (10.2 cm) for the Left Side and Rear, and 12 inches (30.5 cm) from the Right Side
Exhaust Elbow of the water heater be provided for servicing. Clearance for servicing may be reduced
down to minimum clearance to combustible material, but service time and effort may be greatly increased.
5. Increase distances to provide clearance for servicing.