Terminating

# of 90° Elbows

Maximum

Minimum

 

(excluding vent

Length

Length

 

terminal)

 

 

Through the Wall

0

105 ft (32.0 m)

10 ft (3.1 m)

Through the Wall

1

100 ft (30.5 m)

10 ft (3.1 m)

Through the Wall

2

95 ft (29.0 m)

10 ft (3.1 m)

Through the Wall

3

90 ft (27.5 m)

10 ft (3.1 m)

Through the Wall

4

85 ft (26.0 m)

10 ft (3.1 m)

Through the Wall

5

80 ft (24.4 m)

10 ft (3.1 m)

Through the Roof

0

55 ft (16.8 m)

5 ft (1.5 m)

Through the Roof

1

50 ft (15.3 m)

5 ft (1.5 m)

Through the Roof

2

45 ft (13.7 m)

5 ft (1.5 m)

Through the Roof

3

40 ft (12.2 m)

5 ft (1.5 m)

Through the Roof

4

35 ft (10.7 m)

5 ft (1.5 m)

NOTE: When using 3” (7.6 cm) PVC, use a 3” (7.6 cm) to 2” (5.1 cm) reducer and exit the building wall with 2” (5.1 cm) PVC using the 2” (5.1 cm) 45° vent terminal supplied. Two 45° elbows are equivalent to one 90° elbow. Each 90° elbow is equivalent to 5 feet (1.5 m) of straight vent pipe.

Figure 6

IMPORTANT

All of the Venting connections must be leak checked with a soap and water solution upon initial start up of the water heater. Any leaks must be repaired before continuing operation of the water heater.

NOTE: ABS or CPVC pipes may be substituted for PVC pipe. Do not mix

ABS and PVC pipe in the same installation.