Briggs & Stratton Power Products Home Generator
Installation Manual
INSTALLATION PROCEDURES
Required Specialty Tools/Equipment
•Two 48” lengths of 1” OD pipe (NOT conduit)
•Hole punches for 16ga steel
•Torque screwdriver, 5 to 50
Unpacking Precautions
The unit is shipped bolted to its mounting pad, ready for installation. Avoid damage from dropping, bumping, collision, etc. Store and unpack carton with the proper side up, as noted on the shipping carton.
CAUTION
Installing the 15A fuse could cause the engine to start.
•Observe that the 15 Amp fuse has been removed from the control panel for shipping.
•DO NOT install this fuse until all plumbing and wiring has been completed and inspected.
Delivery Inspection
After removing the carton, carefully inspect the Home Standby Generator for any damage that may have occurred during shipment.
IMPORTANT: If loss or damage is noted at time of delivery, have the person(s) making delivery note all damage on the freight bill and affix his signature under the consignor's memo of loss or damage. If loss or damage is noted after delivery, separate the damaged materials and contact the carrier for claim procedures. Missing or damaged parts are not warranted.
Shipment Contents
The Home Standby Generator is supplied with:
•Home Standby Generator
•
•One 24” flexible
•Installation and
•Owner’s manual(P/N 192384GS)
•Illustrated parts list manual (P/N 193208GS for model 01815 or P/N 193918GS for model 01938)
•Product warranty sheet (P/N 190881GS)
•Installation checklist (P/N 190840GS)
•Three access door keys
•Four lifting hole plugs
•Oil fill spout
•
•One spare 15A fuse
•Diagnostic LED kit (diode/plate/decal/pin connectors (2))
Approved Transfer Switches
The Home Standby Generator should be used ONLY with the following UL approved Transfer Switches. Connection to any other transfer switch not listed below will void your equipment warranty.
•50A Nema 1 enclosure, BSPP Model 01917
•50A Nema 3R enclosure, BSPP Model 01918
•100A Nema 3R enclosure, BSPP Model 01813
•100A Nema 3R enclosure w/ main line disconnect, BSPP Model 01928
•200A Nema 3R enclosure, BSPP Model 01814
•200A Nema 3R enclosure w/ main line disconnect, BSPP Model 01929
Home Standby Generator Location
Before installing generator, consult with homeowner and convey the following guidelines which may affect the desired location.
Generator Clearances
The generator enclosure must be at least 5 ft. (152 cm) from structures having combustible walls and/or other combustible materials. Leave at least 3 ft. (92 cm) all around the enclosure including the roof, for adequate cooling, generator maintenance and servicing.
Place generator in a well ventilated area, which will allow for removal of deadly exhaust gas. DO NOT install generator where exhaust gas could accumulate and enter inside or be drawn into a potentially occupied building. Ensure exhaust gas is kept away from any windows, doors, ventilation intakes or other openings that can allow exhaust gas to collect in a confined area (Figure 1). Prevailing winds and air currents should be taken into consideration when positioning generator.
General Location Guidelines
DANGER
Running generator gives off carbon monoxide, an odorless, colorless, poison gas.
Breathing carbon monoxide will cause nausea, fainting or death.
•Operate generator ONLY outdoors.
•Keep exhaust gas from entering a confined area through windows, doors, ventilation intakes or other openings.
4