Briggs & Stratton 040220A manual Fuel Comparison Chart, Withdrawal Rate 32F 20F 10F 30F 40F

Models: 040220A

1 80
Download 80 pages 38.2 Kb
Page 16
Image 16

INSTALLATION

Fuel Comparison Chart

Physical Properties

Propane

Natural Gas

 

 

 

Normal Atmospheric State

Gas

Gas

 

 

 

Boiling Point (in °F):

 

 

Initial

-44

-259

End

-44

-259

 

 

 

Heating Value:

 

 

BTU per gallon (Net LHV*)

83,340

63,310

BTU per Gallon (Gross**)

91,547

 

Cubic Feet (Gas)

2,500

1,000

 

 

 

Density***

36.39

57.75

 

 

 

Weight†

4.24

2.65

 

 

 

Octane Number:

 

 

Research

110+

110+

Motor

97

 

 

 

 

* LHV (Low Heat Value) is the more realistic rating.

** Gross Heat Value does not consider heat lost in the form of water during combustion.

*** Density is given in "Cubic Feet of Gas per Gallon of Liquid".

† Weight is given in "Pounds per Gallon of Liquid".

Size of Propane Tank Required at Various

Temperatures When Kept at Least Half

Full

Given the gas withdrawal rate and the lowest average winter temperature, an installer can specify the required LP storage tank size:

Withdrawal Rate

32°F

20°F

10°F

0°F

-10°F

-30°F

-40°F

50 CFH

115

115

115

250

250

400

600

 

 

 

 

 

 

 

 

100 CFH

250

250

250

400

500

1000

1500

 

 

 

 

 

 

 

 

150 CFH

300

400

500

500

1000

1500

2500

 

 

 

 

 

 

 

 

200 CFH

400

500

750

1000

1200

2000

2500

 

 

 

 

 

 

 

 

300 CFH

750

1000

1500

2000

2500

4000

5000

 

 

 

 

 

 

 

 