GROUNDING THE

GROUNDING THE

BSP5500L Generator

1. Turn the fuel valve to the “On” position (Figure 3).

GENERATOR

The National Electrical Code requires that the frame and external electrically conductive parts of this generator be properly connected to an approved earth ground. Local electrical codes may also require proper grounding of the unit. For that purpose, a GROUNDING WING NUT is provided on the generator end (Figure 2).

Figure 3 — Fuel Valve

Fuel Valve is shown in the Off position

Figure 2 — Grounding Wing Nut

Grounding

Wing Nut

Generally, connecting a No. 12 AWG (American Wire Gauge) stranded copper wire to the grounding wing nut and to an earth–driven copper or brass grounding rod (electrode) provides adequate protection against electrical shock. Be careful to keep the grounding wire attached after connecting the stranded copper wire. However, local codes may vary widely. Consult with a local electrician for grounding requirements in your area.

Properly grounding the generator helps prevent electrical shock if a ground fault condition exists in the generator or in connected electrical devices, especially when the unit is equipped with a wheel kit. Proper grounding also helps dissipate static electricity, which often builds up in ungrounded devices.

OPERATING THE

GENERATOR

GENERATOR CAUTION! Never start or stop the engine with electrical loads connected to the receptacles AND with the connected devices turned ON.

Starting the Engine

2.Place the choke lever in the “Choke” position (Figure 4).

Figure 4 — Choke Lever

3.Set the rocker switch to “On” position (Figure 5).

Figure 5 — Rocker Switch

4.Grasp the recoil handle and pull slowly until slight resistance is felt.Then pull rapidly to start engine.

5.Move choke lever to “Run” position a short distance at a time over several seconds in warm weather or minutes in cold weather. Let engine run smoothly before each change. Operate with choke in “Run” position.

NOTE: If engine still fails to start, see engine manual.This engine may be equipped with a low oil device.

Refer to the engine owner’s manual for more detailed starting instructions.

Disconnect all electrical loads from the generator. Use the following start instruction steps by numerical order: