•Accessory kit containing the following items:
-Console cable
-Wrist strap (ESD grounding strap)
-Ground lug kit
-SFP extraction tool kit
-China RoHS guide
-Cable management finger assemblies
-
-Power cord retainer kit
-Brocade VDX 8770-4 QuickStart Guide (this publication)
-Hardware for securing the switch in a rack
-Web pointer document
-Air filter
The rack mount kits must be ordered separately.
Order the
NOTE
For information about the transceivers that are qualified for the Brocade VDX
Preparing for the Brocade VDX 8770-4 installation
NOTE
Refer to the safety notices before installation (“Safety notices”).
Refer to “Power specifications” to plan for meeting power supply standards before installing the switch. Refer to “Environmental requirements” to plan for your environmental needs.
Refer to “Managing cables” to plan for cable management.
The following steps are required to ensure correct installation and operation.
1.Provide a space that is 8 rack units (8U) high, 61.19 cm (24.09 in.) deep, and 43.74 cm (17.22 in.) wide. One rack unit is equal to 4.45 cm (1.75 in.). If you are using the Air Intake Kit, you will need a space that is 10U high to accommodate both the Intake Kit and the switch.
Plan to install the Brocade VDX
Ensure that the rack is balanced and mechanically secured to provide stability in the event of an earthquake and that the equipment does not exceed the rack’s weight limits.
NOTE
Doorways must be wider than 91 cm (36 in.) to accommodate the switch.
Brocade VDX | 9 of 32 |