116B

REFRIGERANT CHARGE ADJUSTMENTS

Liquid Line Size

Puron Charge oz/ft

 

 

3/8

0.60

(Factory charge for lineset = 9 oz)

 

 

 

5/16

0.40

 

 

1/4

0.27

 

 

Units are factory charged for 15 ft (4.6 m) of 3/8” liquid line. The factory charge for 3/8” lineset 9 oz. When using other length or diameter liquid lines, charge adjustments are required per the chart above.

Charging Formula:

[(Lineset oz/ft x total length) – (factory charge for lineset)] = charge adjustment

Example 1: System has 15 ft of line set using existing 1/4“ liquid line. What charge adjustment is required?

Formula:

(.27 oz/ft x 15ft) – (9 oz) = (-4.95) oz.

Net result is to remove 4.95 oz of refrigerant from the system

Example 2: System has 45 ft of existing 5/16” liquid line. What is the charge adjustment?

Formula:

(.40 oz/ft. x 45ft) – (9 oz.) = 9 oz.

Net result is to add 9 oz of refrigerant to the system

LONG LINE APPLICATIONS

An application is considered Long Line, when the refrigerant level in the system requires the use of accessories to maintain acceptable refrigerant management for systems reliability. See Accessory Usage Guideline table for required accessories. Defining a system as long line depends on the liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units.

For Air Conditioner systems, the chart below shows when an application is considered Long Line.

AC WITH PURONr REFRIGERANT LONG LINE DESCRIPTION ft (m)

Beyond these lengths, long line accessories are required

Liquid Line Size

Units On Same Level

Outdoor Below Indoor

Outdoor Above Indoor

1/4

No accessories needed within allowed

No accessories needed within allowed

175 (53.3)

lengths

lengths

 

 

 

 

 

 

5/16

120 (36.6)

50 (15.2)

120 (36.6)

3/8

80 (24.4)

35 (10.7)

80 (24.4)

Note: See Long Line Guideline for details

VAPOR LINE SIZING AND COOLING CAPACITY LOSS

Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line diameters shown in the chart below are acceptable for AC systems with Puron refrigerant:

Unit

Maximum

Vapor Line

 

 

 

Cooling Capacity Loss (%)

 

 

 

Liquid Line

 

 

 

Total Equivalent Line Length ft. (m)

 

 

 

Nominal

Diameters

 

 

 

 

 

 

Diameters

 

 

 

 

 

 

 

 

 

Size (Btuh)

(In. OD)

26---50

51---80

81---100

101---125

126---150

151---175

176---200

201---225

226---250

(In. OD)

 

 

(7.9---15.2)

(15.5---24.4)

(24.7---30.5)

(30.8---38.1)

(38.4---45.7)

(46.0---53.3)

(53.6---61.0)

(61.3---68.6)

(68.9---76.2)

18000

 

1/2

1

2

3

5

6

7

8

9

11

1 Stage

3/8

5/8

0

1

1

1

2

2

2

3

3

AC with

Puron

 

3/4

0

0

0

0

1

1

1

1

1

24000

 

5/8

0

1

2

2

3

3

4

5

5

1 Stage

3/8

3/4

0

0

1

1

1

1

1

2

2

AC with

Puron

 

7/8

0

0

0

0

0

1

1

1

1

30000

 

5/8

1

2

3

3

4

5

6

7

8

1 Stage

3/8

3/4

0

0

1

1

1

2

2

2

3

AC with

Puron

 

7/8

0

0

0

0

1

1

1

1

1

36000

 

5/8

1

2

4

5

6

8

9

10

12

1 Stage

3/8

3/4

0

1

1

2

2

3

3

4

4

AC with

Puron

 

7/8

0

0

0

1

1

1

1

2

2

42000

 

3/4

0

1

2

2

3

4

4

5

6

1 Stage

3/8

7/8

0

0

1

1

1

2

2

2

3

AC with

Puron

 

1 1/8

0

0

0

0

0

0

0

0

0

48000,

 

3/4

0

1

2

3

4

5

5

6

7

49000

 

 

 

 

 

 

 

 

 

 

 

 

 

7/8

0

0

1

1

2

2

2

3

3

1 Stage

3/8

AC with

 

1 1/8

0

0

0

0

0

0

0

1

1

Puron

 

 

 

 

 

 

 

 

 

 

 

 

60000,

 

3/4

1

2

4

5

6

7

9

10

11

61000

 

 

 

 

 

 

 

 

 

 

 

 

1 Stage

3/8

7/8

0

1

2

2

3

4

4

5

5

AC with

 

1 1/8

0

0

0

1

1

1

1

1

1

Puron

 

 

 

 

 

 

 

 

 

 

 

 

 

Applications in this area may be long line and may have height restrictions. See the Residential Piping and Long Line Guideline.

4

Page 4
Image 4
Bryant 116B manual Long Line Applications, Vapor Line Sizing and Cooling Capacity Loss, Charging Formula