116B

ELECTRICAL DATA

 

 

OPER VOLTS*

COMPR

FAN

 

MIN WIRE

MIN WIRE

MAX

MAX

MAX FUSE**

UNIT SIZE

V/PH

MCA

LENGTH

LENGTH

 

 

 

 

 

SIZE{

SIZE{

or CKT BRK

 

 

 

 

 

ft. (m)}

ft. (m)}

 

 

MAX

MIN

LRA

RLA

FLA

 

60° C

75° C

AMPS

 

 

 

60° C

75° C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

018---B

 

 

 

48.0

9.0

0.50

11.8

14

14

67 (20.4)

64 (19.5)

20

024---A

 

 

 

58.3

13.5

0.75

17.7

14

14

46 (14.0)

43 (13..1)

25

030---A

 

 

 

64.0

12.8

0.75

16.8

14

14

44 (13.4)

41 (12.5)

25

036---A

 

 

 

77.0

14.1

0.50

18.1

12

12

57 (17.4)

54 (16.5)

30

042---A

208/230/1---60 253

197

112.0

17.9

1.20

23.6

10

10

85 (25.9)

81 (24.7)

40

048---B

 

 

 

109.0

19.9

1.20

26.1

10

10

70 (21.3)

67 (20.4)

40

049---A

 

 

 

117.0

21.8

1.20

26.1

10

10

70 (21.3)

67 (20.4)

40

060---A

 

 

 

135.0

21.4

1.20

28.0

8

10

91 (27.7)

56 (17.1)

40

061---A

 

 

 

134.0

25.0

1.20

32.5

8

10

94 (28.7)

58 (17.7)

50

* Permissible limits of the voltage range at which the unit will operate satisfactorily

{If wire is applied at ambient greater than 30_C, consult table 310---16 of the NEC (NFPA 70). The ampacity of non ---metallic---sheathed cable (NM), trade name ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 334---80. If other than uncoated (no---plated), 60 or 75_C insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).

}Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%. ** Time---Delay fuse.

FLA --- Full Load Amps LRA --- Locked Rotor Amps MCA --- Minimum Circuit Amps RLA --- Rated Load Amps

NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

Complies with 2007 requirements of ASHRAE Standards 90.1

A-WEIGHTED SOUND POWER LEVEL (dBA)

Unit Size ---

Standard

 

TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)

 

Voltage, Series

Rating (dBA)

125

250

500

1000

2000

4000

8000

0018---B

76

52.5

59.0

65.5

70.5

64.5

59.0

54.5

0024---A

76

57.5

64.0

69.0

71.0

69.0

64.5

60.0

0030---A

76

55.0

63.5

68.0

69.5

67.0

63.5

58.5

0036---A

76

50.5

59.5

64.5

70.5

62.0

59.5

54.5

0042---A

78

52.5

62.0

66.0

73.5

68.0

62.0

55.5

0048---B

78

57.5

61.5

66.0

70.5

65.5

59.5

53.5

0049---A

78

51.5

62.0

67.5

73.5

69.0

64.5

62.0

0060---A

78

55.0

62.5

67.5

70.5

65.0

61.0

53.5

0061---A

78

56.5

63.0

65.5

69.0

67.0

61.5

56.0

NOTE: Tested in accordance with AHRI Standard 270---08 (not listed in AHRI).

A-WEIGHTED SOUND POWER LEVEL (dBA) WITH SOUND SHIELD

Unit Size ---

Standard

 

TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)

 

Voltage, Series

Rating (dBA)

125

250

500

1000

2000

4000

8000

0018---B

74

55.5

59.0

65.0

68.5

63.5

58.0

52.0

0024---A

75

58.0

64.0

69.0

70.5

68.5

64.5

59.5

0030---A

75

55.5

63.0

68.0

69.0

67.0

63.0

58.5

0036---A

74

51.5

58.5

62.0

65.0

61.0

58.0

52.0

0042---A

76

53.0

62.0

65.5

72.0

65.0

61.0

54.0

0048---B

76

58.5

61.5

66.0

69.0

64.0

58.5

51.0

0049---A

76

53.0

61.5

67.5

72.0

68.0

61.5

59.0

0060---A

75

56.5

62.5

66.5

68.0

63.0

59.5

51.5

0061---A

75

57.0

63.0

65.5

67.0

65.5

59.0

52.5

NOTE: Tested in accordance with AHRI Standard 270---08 (not listed in AHRI).

CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE)

UNIT SIZE---VOLTAGE, SERIES

REQUIRED SUBCOOLING _F (_C)

018---B

10 (5.6)

024---A

10 (5.6)

030---A

10 (5.6)

036---A

10 (5.6)

042---A

9 (5.0)

048---B

10 (5.6)

049---A

8 (4.4)

060---A

9 (5.0)

061---A

9 (5.0)

8

Page 8
Image 8
Bryant 116B manual Electrical Data, Charging Subcooling TXV-TYPE Expansion Device, Max Min Lra Rla Fla, Amps