17
DETAILED COOLING CAPACITIES# (CONT.)
EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
CFM EWB
°F(°C)
Capacity MBtuh† Tota l
System
KW**
Capacity MBtuh† Tota l
System
KW**
Capacity MBtuh† To t al
System
KW**
Capacity MBtuh† Tota l
System
KW**
Capacity MBtuh† Tota l
System
KW**
Capacity MBtuh† Tota l
System
KW**
Tota l Sens‡ Tot al Sens‡ Tot a l Sens‡ Tot a l Sens‡ Tot al Sens‡ Tot a l Sens‡
116BNA061****A Outdoor Section With CNPV*6124A**+TDR Indoor Section
1750
72 (22.2) 68.26 35.40 3.65 65.62 34.24 4.19 62.70 33.02 4.80 59.44 31.72 5.50 55.84 30.35 6.31 51.84 28.89 7.25
67 (19.4) 62.16 43.65 3.59 59.80 42.52 4.12 57.18 41.32 4.72 54.27 40.05 5.42 51.03 38.69 6.24 47.43 37.23 7.18
62 (16.7) 56.92 51.79 3.54 54.89 50.66 4.07 52.67 49.40 4.67 50.45 50.45 5.37 48.08 48.08 6.19 45.35 45.35 7.15
57 (13.9) 55.79 55.79 3.53 54.23 54.23 4.06 52.43 52.43 4.67 50.37 50.37 5.37 48.01 48.01 6.19 45.29 45.29 7.15
2000
72 (22.2) 69.37 37.22 3.75 66.58 36.03 4.29 63.50 34.78 4.91 60.12 33.47 5.61 56.36 32.08 6.43 52.22 30.60 7.37
67 (19.4) 63.22 46.57 3.69 60.75 45.42 4.22 58.00 44.20 4.83 54.96 42.90 5.54 51.60 41.51 6.35 47.88 40.00 7.30
62 (16.7) 58.30 55.64 3.64 56.40 56.40 4.18 54.43 54.43 4.79 52.18 52.18 5.50 49.62 49.62 6.32 46.69 46.69 7.28
57 (13.9) 58.04 58.04 3.64 56.32 56.32 4.17 54.35 54.35 4.79 52.12 52.12 5.50 49.56 49.56 6.32 46.64 46.64 7.28
2250
72 (22.2) 70.16 38.93 3.85 67.25 37.73 4.39 64.06 36.47 5.01 60.55 35.14 5.72 56.68 33.73 6.54 52.43 32.24 7.48
67 (19.4) 64.02 49.36 3.79 61.43 48.19 4.32 58.58 46.94 4.94 55.46 45.61 5.65 52.01 44.17 6.47 48.25 42.59 7.41
62 (16.7) 59.97 59.97 3.75 58.12 58.12 4.29 55.99 55.99 4.91 53.58 53.58 5.62 50.85 50.85 6.45 47.74 47.74 7.41
57 (13.9) 59.89 59.89 3.75 58.04 58.04 4.29 55.93 55.93 4.91 53.52 53.52 5.62 50.79 50.79 6.45 47.69 47.69 7.40
{Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
}Sensible capacities shown are based on 80_F(27_C) entering air at the indoor coil. For sensible capacities at other than 80_F(27_C), deduct 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below
80_F(27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F(27_C).
# Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per AHRI standard 210/240--- 2008. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity
may occur.
** System kw is total of indoor and outdoor unit kilowatts.
{{ At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb.
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
EWB — Entering Wet Bulb
116B