213A
DETAILED COOLING CAPACITIES CONTINUED
EVAPORATOR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| CONDENSER ENTERING AIR TEMPERATURES deg F |
|
|
|
|
|
| |||||||||
AIR |
|
|
| 75 |
|
|
|
| 85 |
|
|
|
|
|
| 95 |
|
| 105 |
|
| 115 |
|
| 125 |
| |||||
|
|
|
|
| Capacity |
| Total |
| Capacity |
| Total |
|
| Capacity | Total | Capacity | Total | Capacity | Total | Capacity | Total | ||||||||||
CFM | EWB |
|
| MBtuh† | System |
| MBtuh† |
| System |
|
| MBtuh† | System | MBtuh† | System | MBtuh† | System | MBtuh† | System | ||||||||||||
|
|
| Total | Sens‡ |
| KW** |
| Total |
| Sens‡ |
| KW** |
|
| Total | Sens‡ | KW** | Total | Sens‡ | KW** | Total | Sens‡ | KW** | Total | Sens‡ | KW** | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
|
| 72 |
|
| 71.08 |
| 36.09 |
| 4.41 |
| 67.69 |
| 34.77 |
| 4.86 |
| 64.09 | 33.39 | 5.36 | 60.33 | 31.96 | 5.90 | 56.30 | 30.45 | 6.50 | 51.84 | 28.81 | 7.14 | |||
|
| 67 |
|
| 65.19 |
| 45.05 |
| 4.36 |
| 62.05 |
| 43.69 |
| 4.81 |
| 58.73 | 42.27 | 5.30 | 55.30 | 40.82 | 5.85 | 51.61 | 39.29 | 6.44 | 47.57 | 37.62 | 7.09 | |||
1750 |
| 63 |
|
| 60.79 |
| 43.67 |
| 4.31 |
| 57.85 |
| 42.31 |
| 4.76 |
| 54.78 | 40.90 | 5.26 | 51.57 | 39.45 | 5.81 | 48.15 | 37.91 | 6.40 | 44.41 | 36.26 | 7.05 | |||
|
| 62 |
|
| 59.61 |
| 53.90 |
| 4.30 |
| 56.75 |
| 52.49 |
| 4.75 |
| 53.77 | 51.00 | 5.25 | 50.69 | 49.41 | 5.80 | 47.50 | 47.50 | 6.40 | 45.90 | 45.90 | 6.36 | |||
|
| 57 |
|
| 57.48 |
| 57.48 |
| 4.28 |
| 55.20 |
| 55.20 |
| 4.74 |
| 52.79 | 52.79 | 5.24 | 50.24 | 50.24 | 5.79 | 47.49 | 47.49 | 6.40 | 44.42 | 44.42 | 7.06 | |||
|
| 72 |
|
| 72.12 |
| 37.62 |
| 4.54 |
| 68.55 |
| 36.26 |
| 4.99 |
| 64.87 | 34.89 | 5.48 | 60.98 | 33.44 | 6.03 | 56.80 | 31.91 | 6.62 | 52.19 | 30.25 | 7.26 | |||
|
| 67 |
|
| 66.24 |
| 47.72 |
| 4.48 |
| 62.96 |
| 46.34 |
| 4.93 |
| 59.50 | 44.89 | 5.43 | 55.93 | 43.42 | 5.97 | 52.11 | 41.85 | 6.57 | 47.93 | 40.14 | 7.21 | |||
2000 |
| 63 |
|
| 61.83 |
| 46.19 |
| 4.44 |
| 58.77 |
| 44.80 |
| 4.89 |
| 55.56 | 43.36 | 5.38 | 52.22 | 41.88 | 5.93 | 48.67 | 40.31 | 6.53 | 44.80 | 38.60 | 7.18 | |||
|
| 62 |
|
| 60.73 |
| 57.58 |
| 4.43 |
| 57.79 |
| 56.05 |
| 4.88 |
| 54.77 | 54.33 | 5.38 | 51.88 | 51.88 | 5.93 | 48.94 | 48.94 | 6.53 | 47.37 | 47.37 | 6.51 | |||
|
| 57 |
|
| 59.63 |
| 59.63 |
| 4.42 |
| 57.18 |
| 57.18 |
| 4.87 |
| 54.60 | 54.60 | 5.38 | 51.89 | 51.89 | 5.93 | 48.94 | 48.94 | 6.53 | 45.66 | 45.66 | 7.19 | |||
|
| 72 |
|
| 72.83 |
| 39.05 |
| 4.66 |
| 69.16 |
| 37.69 |
| 5.11 |
| 65.40 | 36.31 | 5.61 | 61.39 | 34.85 | 6.15 | 57.10 | 33.30 | 6.74 | 52.35 | 31.61 | 7.37 | |||
|
| 67 |
|
| 66.96 |
| 50.26 |
| 4.61 |
| 63.58 |
| 48.86 |
| 5.06 |
| 60.01 | 47.39 | 5.55 | 56.35 | 45.89 | 6.09 | 52.43 | 44.28 | 6.69 | 48.14 | 42.52 | 7.33 | |||
2250 |
| 63 |
|
| 62.58 |
| 48.57 |
| 4.56 |
| 59.40 |
| 47.16 |
| 5.01 |
| 56.09 | 45.69 | 5.51 | 52.66 | 44.18 | 6.05 | 49.01 | 42.56 | 6.65 | 45.05 | 40.80 | 7.30 | |||
|
| 62 |
|
| 61.68 |
| 60.83 |
| 4.56 |
| 58.79 |
| 58.79 |
| 5.01 |
| 56.05 | 56.05 | 5.51 | 53.19 | 53.19 | 6.06 | 50.08 | 50.08 | 6.66 | 46.62 | 46.62 | 7.31 | |||
|
| 57 |
|
| 61.37 |
| 61.37 |
| 4.55 |
| 58.79 |
| 58.79 |
| 5.01 |
|
| 56.06 | 56.06 | 5.51 | 53.19 | 53.19 | 6.06 | 50.08 | 50.08 | 6.66 | 46.62 | 46.62 | 7.31 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
Cooling Indoor Model |
|
| Capacity |
| Power |
|
| Furnace Model |
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
| *FY4ANB060 |
|
| 1.00 | 1.00 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
| FV4BNB006 |
|
| 1.01 | 0.95 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
FX4CN(B,F)060 |
| 1.01 | 0.91 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
CAP**6021A** |
| 0.99 | 0.99 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
CAP**6024A** |
| 1.01 | 1.01 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
CNPH*6024A** |
| 1.00 | 1.00 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
CNPV*6024A** |
| 1.00 | 1.00 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
CSPH*6012A** |
| 1.01 | 1.01 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
CAP**6021A** |
| 0.97 | 0.94 |
|
|
| 315(A,J)AV060110 |
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
CNPH*6024A** |
| 0.98 | 0.95 |
|
|
| 315(A,J)AV060110 |
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
CSPH*6012A** |
| 0.99 | 0.96 |
|
|
| 315(A,J)AV060110 |
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
CAP**6024A** |
| 0.99 | 0.93 |
|
|
| 315(A,J)AV066135 |
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
CNPH*6024A** |
| 0.98 | 0.95 |
|
|
| 315(A,J)AV066135 |
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
CNPV*6024A** |
| 0.98 | 0.95 |
|
|
| 315(A,J)AV066135 |
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
CSPH*6012A** |
| 0.99 | 0.93 |
|
|
| 315(A,J)AV066135 |
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
CAP**6024A** |
| 0.99 | 0.93 |
|
|
| 315(A,J)AV066155 |
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
CNPH*6024A** |
| 0.99 | 0.93 |
|
|
| 315(A,J)AV066155 |
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
CNPV*6024A** |
| 0.99 | 0.93 |
|
|
| 315(A,J)AV066155 |
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
CSPH*6012A** |
|
| 0.99 | 0.93 |
|
|
| 315(A,J)AV066155 |
|
|
|
|
|
|
|
|
|
|
|
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
*Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard
{Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
}Sensible capacities shown are based on 80_F (27_C) entering air at the indoor coil. For sensible capacities at other than 80_F (27_C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F (27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F (27_C).
** System kw is total of indoor and outdoor unit kilowatts.
{{At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb. EWB — Entering Wet Bulb
24